60
YORK INTERNATIONAL
the rate of drop in water temperature exceeds 2X the
programmed Rate Sensitivity, no further loading or un-
loading will result since the micro sees the temperature
dropping at an excessive rate anticipating temperature
will soon fall into the CONTROL RANGE.
The micro is capable of providing 5, 7, or 10 steps of
loading/unloading. The chiller MUST be programmed for
the number of steps which were ordered. Otherwise,
improper operation and water temperature control prob-
lems will result.
NOTE. The micro controls loading and unloading re-
sponses on a 10 step scale regardless of the
number of stages present. Therefore, loading
and unloading responses on 5 & 7 step chillers
may appear delayed (time between steps in-
creased) when missing steps are activated or
de-activated by the micro, 5 STEP CONTROL
IS STANDARD.
Fig. 20 shows the loading and unloading sequences for
5, 7 and 10 steps of control.
FIG. 20 – LEAVING WATER CONTROL LOADING/UNLOADING
5 STEP (STANDARD)
TEMPERATURE
RISE
LOAD
UNLOAD
5
LEAD COMP + 1 STEP,
LAG COMP + 1 STEP
– – –
– – – – – – – – – – – – – – – – – –
4
LEAD COMP + 1 STEP,
LAG COMP UNLOADED – – –
LEAD COMP + 1 STEP,
LAG COMP UNLOADED
3
LEAD COMP UNLOADED, LAG COMP UNLOADED – – –
LEAD COMP UNLOADED, LAG COMP UNLOADED
2
LEAD COMP + 1 STEP,
LAG COMP OFF
– – –
LEAD COMP + 1 STEP,
LAG COMP OFF
1
LEAD COMP UNLOADED, LAG COMP OFF
– – –
LEAD COMP UNLOADED, LAG COMP OFF
LEAD COMP OFF,
LAG COMP OFF
– – –
LEAD COMP OFF,
LAG COMP OFF
TEMPERATURE
FALL
7 STEP (OPTIONAL)
TEMPERATURE
RISE
LOAD
UNLOAD
7
LEAD COMP + 2 STEPS,
LAG COMP + 2 STEPS
– – –
– – – – – – – – – – – – – – – – – –
6
LEAD COMP + 2 STEPS,
LAG COMP + 1 STEP
– – –
LEAD COMP + 2 STEPS,
LAG COMP + 1 STEP
5
LEAD COMP + 1 STEP,
LAG COMP + 1 STEP
– – –
LEAD COMP + 1 STEP,
LAG COMP + 1 STEP
4
LEAD COMP + 1 STEP,
LAG COMP UNLOADED – – –
LEAD COMP + 1 STEP,
LAG COMP UNLOADED
3
LEAD COMP + 2 STEPS,
LAG COMP OFF
– – –
– – – – – – – – – – – – – – – – – – *
2
LEAD COMP + 1 STEP,
LAG COMP OFF
– – –
LEAD COMP + 1 STEP,
LAG COMP OFF
1
LEAD COMP UNLOADED, LAG COMP OFF
– – –
LEAD COMP UNLOADED, LAG COMP OFF
LEAD COMP OFF,
LAG COMP OFF
– – –
LEAD COMP OFF,
LAG COMP OFF
TEMPERATURE
FALL
10 STEP (OPTIONAL)
TEMPERATURE
RISE
LOAD
UNLOAD
10
LEAD COMP + 3 STEPS,
LAG COMP + 3 STEPS
– – –
– – – – – – – – – – – – – – – – – –
9
LEAD COMP + 3 STEPS,
LAG COMP + 2 STEPS
– – –
LEAD COMP + 3 STEPS,
LAG COMP + 2 STEPS
8
LEAD COMP + 2 STEPS,
LAG COMP + 2 STEPS
– – –
LEAD COMP + 2 STEPS,
LAG COMP + 2 STEPS
7
LEAD COMP + 2 STEPS,
LAG COMP + 1 STEP
– – –
LEAD COMP + 2 STEPS,
LAG COMP + 1 STEP
6
LEAD COMP + 1 STEP,
LAG COMP + 1 STEP
– – –
LEAD COMP + 1 STEP,
LAG COMP + 1 STEP
5
LEAD COMP + 1 STEP,
LAG COMP UNLOADED – – –
LEAD COMP + 1 STEP,
LAG COMP UNLOADED
4
LEAD COMP + 3 STEPS,
LAG COMP OFF
– – –
– – – – – – – – – – – – – – – – – – *
3
LEAD COMP + 2 STEPS,
LAG COMP OFF
– – –
LEAD COMP + 2 STEPS,
LAG COMP OFF
2
LEAD COMP + 1 STEP,
LAG COMP OFF
– – –
LEAD COMP + 1 STEP,
LAG COMP OFF
1
LEAD COMP UNLOADED, LAG COMP OFF
– – –
LEAD COMP UNLOADED, LAG COMP OFF
LEAD COMP OFF,
LAG COMP OFF
– – –
LEAD COMP OFF,
LAG COMP OFF
TEMPERATURE
FALL
* This step is skippped on a temperature drop.
Содержание Millennium YCAJ150
Страница 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Страница 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Страница 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Страница 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Страница 26: ...26 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING LD02464...
Страница 28: ...28 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING Cont d LD02650...
Страница 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Страница 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Страница 101: ...FORM 150 65 NM4 101 YORK INTERNATIONAL LD02655 FIG 37C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Страница 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Страница 105: ...FORM 150 65 NM4 105 YORK INTERNATIONAL LD02657 FIG 39C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 107: ...FORM 150 65 NM4 107 YORK INTERNATIONAL FIG 40A CONDENSER COIL LOUVER INSTALLATION SIDES LD02658...
Страница 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Страница 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...