88
YORK INTERNATIONAL
OPTIONS
FIG. 29 – CONDENSER WATER PUMP CONTACT
CONNECTION POINT
LD02097
LD02098
FIG. 30 – CONDENSER WATER PUMP CONTACT
CONNECTION POINT
This section is devoted to options which may be ordered or retrofitted to the unit. Listed below are the options which
are covered in this section.
1.
CONDENSER WATER PUMP / RUN STATUS CONTACT OPTION
Both controls are included as part
2.
EVAPORATOR WATER PUMP CONTACT OPTION
of the PUMP CONTROL KIT
3.
LOW AMBIENT ACCESSORY
4.
HOT GAS BYPASS (LOADMINDER) OPTION
5.
DISCHARGE PRESSURE READOUT OPTION
6.
HIGH AMBIENT OPTION
7.
LOCAL PRINTER OPTION
8.
OPTIONAL TAMPERPROOF ENCLOSURE (WIRE GRILLE)
9.
OPTIONAL DECORATIVE TAMPERPROOF ENCLOSURE (LOUVERED & WIRE GRILLE)
10.
OPTIONAL DECORATIVE TAMPERPROOF ENCLOSURE (LOUVERED)
11.
OPTIONAL TAMPERPROOF CONDENSER COIL ENCLOSURE (LOUVERED)
12.
BAS INTERFACE OPTION (REMOTE RESET OPTION)
CONDENSER WATER PUMP
CONTACT/RUN STATUS OPTION
This option provides a “dry” contact which can be used
to turn on the condenser water pump other device. The
contact closes whenever one of the compressors starts.
Connections to this contact can be made on Terminals
21 and 22 of TB1 in the power panel. The location of
these terminals is shown in Fig. 29.
This option utilizes a second Relay Output Board and
associated wiring. The part number for the Field Mounted
Pump Control Kit is 471-01232-101. This kit is not re-
quired if a second Relay Output Board is already installed.
NOTE: Any inductive devices (contactor/relay coil) con-
nected to these contacts must be suppressed
with YORK P/N 031-00808 supplied by others.
Otherwise, nuisance faults may occur.
EVAPORATOR WATER PUMP CONTACT OPTION
This option provides a “dry” contact which can be used
to turn on the evaporator water pump. The contact will
be closed by the micro before the micro brings a com-
pressor on. The micro will not bring a compressor on
until a “RUN PERMISSIVE” signal is established by a
flow switch contact closure. If no daily schedule is set
(all times = 00.00), the evaporator water pump contact
will transition as soon as a System Switch on the micro-
processor board is placed in the ON position.
If a daily schedule is programmed, the evaporator water
pump contacts will transition when the daily schedule
dictates.
If MANUAL OVERRIDE is selected, the evaporator wa-
ter pump contacts will immediately transition.
Содержание Millennium YCAJ150
Страница 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Страница 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Страница 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Страница 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Страница 26: ...26 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING LD02464...
Страница 28: ...28 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING Cont d LD02650...
Страница 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Страница 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Страница 101: ...FORM 150 65 NM4 101 YORK INTERNATIONAL LD02655 FIG 37C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Страница 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Страница 105: ...FORM 150 65 NM4 105 YORK INTERNATIONAL LD02657 FIG 39C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 107: ...FORM 150 65 NM4 107 YORK INTERNATIONAL FIG 40A CONDENSER COIL LOUVER INSTALLATION SIDES LD02658...
Страница 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Страница 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...