10
YORK INTERNATIONAL
DIMENSIONS
(English)
LD01192
LD01193
LD01194
LD01195
CHILLER
X
J150
1'–5"
J160
1'–5"
J180
1'–6"
J190
1'–6"
J200
1'–6-1/2"
J220
1'–6-1/2"
J230
1'–6-1/2"
WEIGHT DISTRIBUTION (LBS.)
WATER
CONN.
MODEL YCA
INLET/OUTLET
A
B
C
D
E
F
G
H
DIA. (INCHES)
J150
1791
1813
1843
2130
1738
1872
1893
2011
8
J160
1883
1915
1951
2228
1804
1948
1976
2089
8
J180
1939
1984
2000
2265
1979
2181
2197
2252
8
J190
1939
1984
2002
2272
1979
2181
2199
2259
8
J200
2025
2078
2093
2366
2125
2361
2377
2419
8
J220
2025
2078
2093
2366
2125
2361
2377
2419
8
J230
2094
2147
2163
2441
2156
2393
2435
2461
8
NOTES:
1. Clearances – Recommended YORK clearances for peak per-
formance, reliable operation, and maintenance: Side to wall – 8';
Rear to wall – 8'; Control panel end to wall – 5'; Over the top –
no obstructions allowed; Two units side by side – 12', (walls
should be no higher than the unit). The area within the clearances
and under the unit(s) must be kept clean of clutter. Additional
height should be included to allow for snow accumulation for
units which are expected to operate at full load during the winter.
Reduced clearances may be used due to jobsite restrictions.
The unit(s) with optional controls will allow optimal operation pre-
venting the condenser pressure from exceeding the maximum
limit. The units will continue to operate without nuisance high
pressure cutout even though the airflow may be restricted at
these conditions.
2. Panel bottom to be punched in field to accommodate power wir-
ing conduit.
3. Use of isolators (optional) will increase height of unit approxi-
mately 6".
4. Drawings not to scale and are for planning purposes only. Con-
tact nearest YORK Sales Office for detailed drawings.
CAUTION
FAILURE TO HEED ABOVE RECOMMENDED CLEARANCES MAY RESULT IN
REDUCED SYSTEM PERFORMANCE, NUISANCE SHUTDOWNS, AND SERVICE PROBLEMS.
Содержание Millennium YCAJ150
Страница 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Страница 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Страница 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Страница 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Страница 26: ...26 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING LD02464...
Страница 28: ...28 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING Cont d LD02650...
Страница 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Страница 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Страница 101: ...FORM 150 65 NM4 101 YORK INTERNATIONAL LD02655 FIG 37C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Страница 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Страница 105: ...FORM 150 65 NM4 105 YORK INTERNATIONAL LD02657 FIG 39C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 107: ...FORM 150 65 NM4 107 YORK INTERNATIONAL FIG 40A CONDENSER COIL LOUVER INSTALLATION SIDES LD02658...
Страница 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Страница 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...