FORM 150.65-NM4
35
YORK INTERNATIONAL
on each compressor are also displayed. A total of 99999
starts can be logged on a system before the counter will
rollover.
The numbers “1” and “2” on the display message indi-
cate compressor #1 and compressor #2.
These counters are zeroed at the factory or will indicate
only run time and number of starts logged during factory
testing at the time of shipment.
Options
The OPTIONS key provides a display of options which
have been selected by the user. These options are se-
lected by the S1 Dip Switch on the Microprocessor Board
(Fig. 13). Proper programming of the switch is important
during commissioning of the chiller. The OPTIONS dis-
play allows a means of verifying the Dip Switch posi-
tions without looking at or handling the Microprocessor
Board. It also eliminates visual inspection of the some-
times difficult to determine Dip Switch position.
When the OPTIONS key is pressed, the following mes-
sage will first be displayed for 3 seconds:
“8” Option Messages will then follow. Each will be dis-
played for 3 seconds before the next display is auto-
matically indexed. When all messages are displayed,
the display message will automatically change to show
a chiller “STATUS” message, just as if the STATUS key
was pressed.
Refer to Table 1 for a list of the displays and the corre-
sponding switch positions in the order they appear. Two
possible messages may appear for each of the eight
messages depending on the Dip Switch position.
A detailed explanation of the meaning of each message
and a guide to programming the associated switch is
provided on page 37.
Fig. 13 shows the location and verification of switch po-
sitioning of S1.
The minimum limits are:
Oil Pressure: 0 PSID (0 bar)
Suction Pressure: 0 PSIG (0 bar)
Discharge Pressure: 0 PSIG (0 bar)
The maximum limits are:
Oil Pressure: 200 PSID (13.8 bar)
Suction Pressure: 200 PSIG (13.8 bar)
Discharge Pressure: 400 PSIG (27.6 bar)
System 2 Pressures
Oil pressure, suction pressure, and discharge* pressure
on System 2 will be displayed when this push-button is
pressed.
The minimum limits are:
Oil Pressure: 0 PSID (0 bar)
Suction Pressure: 0 PSIG (0 bar)
Discharge Pressure: 0 PSIG (0-bar)
The maximum limits are:
Oil Pressure: 200 PSID (13.8 bar)
Suction Pressure: 200 PSIG (13.8 bar)
Discharge Pressure: 400 PSIG (27.6 bar)
% Motor Current
Motor currents for both System 1 and 2 are displayed
when this push-button is pushed.
The minimum limits on the display is “0% FLA”. The
maximum limit on the display is “115% FLA”.
Operating Hours
Start Counter
Accumulated running hours on each compressor is dis-
played. The counters for an individual system count to a
total of 99999 hours before rollover. Accumulated starts
S Y S
# 2
O I L =
6 3
P S I D
S P =
6 1 , D P =
1 3 3
P S I G
SYSTEM 2
PRESSURES
% MOTOR
CURRENT
H R S
1 =
1 4 3 ,
2 =
3 8 2
S T R
1 =
2 5 ,
2 =
3 7
OPER. HOURS
START COUNTER
T H E
F O L L O W I N G
A R E
P R O G R A M M E D
1 M T R 1
=
5 7
% F L A
1 M T R 2
=
6 5
% F L A
OPTIONS
* Discharge Pressure Readout is an option. Without this option, the display will read a fixed value.
Содержание Millennium YCAJ150
Страница 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Страница 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Страница 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Страница 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Страница 26: ...26 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING LD02464...
Страница 28: ...28 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING Cont d LD02650...
Страница 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Страница 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Страница 101: ...FORM 150 65 NM4 101 YORK INTERNATIONAL LD02655 FIG 37C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Страница 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Страница 105: ...FORM 150 65 NM4 105 YORK INTERNATIONAL LD02657 FIG 39C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 107: ...FORM 150 65 NM4 107 YORK INTERNATIONAL FIG 40A CONDENSER COIL LOUVER INSTALLATION SIDES LD02658...
Страница 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Страница 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...