YORK INTERNATIONAL
UNIT ON/OFF SWITCH
A master UNIT ON/OFF switch is located on the key-
pad. This rocker switch allows the operator to turn the
entire chiller OFF if desired. The switch must be placed
in the ON position for the chiller to operate.
Whenever the switch is placed in the OFF position, a
STATUS display indicating the condition will be displayed.
This message is shown below.
SYSTEM SWITCHES
SYSTEM SWITCHES 1-4 are located on the Micropro-
cessor Board (See Fig. 23). These allow the operator to
selectively turn a given system on or off as desired. On a
2 system chiller, switches 3 & 4 should be OFF. The
System Switch for a designated system must be ON
(Switch to right) for the system to operate.
Whenever a switch is placed in the OFF position, a STA-
TUS display indicating the condition will be displayed
indicating that the system does not have a Run Permis-
sive signal. A sample of this message is shown below.
NOTE: This message will not appear if Anti-recycle or
Anti-coincident timers are in effect and are be-
ing displayed.
“UNIT” ON/OFF SWITCH
U N I T
S W I T C H
I S
I N
T H E
O F F
P O S I T I O N
S Y S # 1
N O
R U N
P E R M
S Y S # 2
N O
R U N
P E R M
ALARM CONTACTS (ANNUNCIATION ALARM)
“Dry” contacts connected to terminals 23 and 24 (Fig.
24) are supplied, which will transition to function as a
warning whenever a fault shutdown occurs on any sys-
tem or if power is lost to the control panel. The dry con-
tacts are normally open (N.O.) and will close when con-
trol power is applied to the panel, if no fault conditions
are present. If power is not lost or a fault lockout occurs,
the contact will open.
A 28VDC or 120VAC external alarm circuit (by others)
may be wired into the YORK supplied alarm contacts.
Any inductive load devices (relay, contactor), supplied
by the user which are connected to the dry contacts,
MUST be suppressed at the load. Use YORK P/N 031-
00808-000 suppressor (not supplied). Failure to do this
will result in nuisance faults and possible damage to the
chiller.
CAUTION: If the alarm circuit is applied in an applica-
tion used for critical duty (such as process
duty or cooling other critical equipment) and
the alarm circuit should fail to function,
YORK will not be liable for damages.
LEAD/LAG COMPRESSOR SELECTION
The Chiller may be set up for AUTO or MANUAL Lead/
Lag. This is accomplished by properly configuring the
S1 Dip Switches on the Microprocessor Board. Details
for configuring the switches are discussed in the DIS-
PLAY KEY Section of the IOM under the “OPTIONS”
key.
02711TG
“UNIT”
ON/OFF
SWITCH
Содержание Millennium YCAJ150
Страница 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Страница 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Страница 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Страница 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Страница 26: ...26 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING LD02464...
Страница 28: ...28 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING Cont d LD02650...
Страница 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Страница 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Страница 101: ...FORM 150 65 NM4 101 YORK INTERNATIONAL LD02655 FIG 37C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Страница 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Страница 105: ...FORM 150 65 NM4 105 YORK INTERNATIONAL LD02657 FIG 39C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 107: ...FORM 150 65 NM4 107 YORK INTERNATIONAL FIG 40A CONDENSER COIL LOUVER INSTALLATION SIDES LD02658...
Страница 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Страница 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...