84
YORK INTERNATIONAL
5.
After 4 seconds of run time, the motor current
of the lead compressor must be > 14% FLA and
< 115% FLA. Oil pressure must be > 5 PSID (34.5
kPa). If these conditions are not met, the lead
compressor will shut down.
6.
After 30 seconds of run time, the oil pressure
of the lead compressor must be > 20 PSID (137.9
kPa) and the suction pressure must be > 50% of
cutout. If these conditions are not met, the lead
compressor will shut down.
7.
After 1 minute of run time, the lead compres-
sor will load the 1st step, if cooling demand (tem-
perature and rate control) requires.
8.
After 2 minutes of run time, the lead compres-
sor will load the 2nd step, if cooling demand (tem-
perature and rate control) requires.
9.
After 3 minutes of run time, the lead compres-
sor will load its 3rd step, if temperature demand
(temperature and rate control) requires.
10.
After 4 minutes of operation, the oil pressure
of the lead compressor must be >25 PSID (172.4
kPa) and the suction pressure must be > cutout.
If these conditions are not met, the lead com-
pressor will shut down. If cooling demand requires
(temperature and rate control), the lag compres-
sor will start unloaded and its anti-recycle counter
will begin counting back to “0”. The liquid line so-
lenoid will open. The lead compressor will unload
2 steps to its 1st step of 3 loading steps.
11.
After 4 minutes and 4 seconds of run time,
the motor current of the lag compressor must be
>14% FLA and < 115% FLA. Oil pressure must
be > 5 PSID (34.5 kPa). If these conditions are
not met, the lag compressor will shut down.
12.
After 4 minutes and 30 seconds of run time,
the oil pressure of the lag compressor must be
>20 PSID (137.9 kPa) and the suction pressure
must be > 50% cutout. If these conditions are not
met, the lag compressor will shut down.
13.
After 5 minutes of run time, the lag compres-
sor will load to the 1st step of loading, if cooling
demand requires (temperature and rate control).
The lead compressor remains unchanged at the
1st step of loading.
14.
After 6 minutes of run time, the lead compres-
sor will load to its 2nd step of loading, if cooling
demand requires (temperature and rate control).
The lag compressor remains unchanged at the
1st step of loading.
15.
After 7 minutes of run time, the lag compres-
sor will load to its 2nd step of loading, if cooling
demand requires.
16.
After 8 minutes of operation, the oil pressure
of the lag compressor must be > 25 PSID (172.4
kPa) and the suction pressure must be > cutout .
If these conditions are not met, the lag compres-
sor will shut down (temperature and rate control).
The lead compressor will load to its 3rd and final
step of loading, if cooling demand requires (tem-
perature and rate control). The lag compressor
remains unchanged at the 2nd step of loading.
17.
After 9 minutes of run time, the lag compres-
sor will load its 3rd and final step, if cooling de-
mand requires (temperature and rate control). The
lead compressor remains unchanged at the 3rd
step of loading.
OPERATING SEQUENCE UTILIZING
LEAVING WATER CONTROL
NOTE: The operating sequence described below relates
to operation after power has been applied on a
hot water start such as at start-up commission-
ing or a hot water start up at the beginning of
the day. It also assumes that 10 steps of load-
ing are available and programmed. If less than
10 steps are available, no chiller response will
take place at some of the operating points de-
scribed.
1.
For the system compressors to run, all Manual
Reset Cut-outs must be reset, the Flow Switch
must be closed, any Remote Cycling Contracts
must be closed, the System Switches must be
ON, the Daily Schedule must be scheduling the
chiller to run, and temperature demand must be
present.
2.
As long as power is applied, the Crankcase Heat-
ers will be on and stay on as long as the com-
pressors are not running.
3.
If power has just been applied to the system, the
microprocessor will start a 2-minute timer. This is
the same timer that prevents an instantaneous
start after a power failure. NOTE: Compressor
Crankcase Heaters should be on for a period of
24 hours prior to commissioning. Failure to allow
the heater sufficient time to warm the oil may
damage the compressor due to liquid refrigerant
in the oil.
4.
At the end of the 2 minute timer, the micropro-
cessor will check for cooling demand as well as
check to see if any system safeties have been
Содержание Millennium YCAJ150
Страница 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Страница 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Страница 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Страница 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Страница 26: ...26 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING LD02464...
Страница 28: ...28 YORK INTERNATIONAL CONNECTION DIAGRAM TERMINAL BOX AND SYSTEM WIRING FIG 8 SYSTEM WIRING Cont d LD02650...
Страница 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Страница 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Страница 101: ...FORM 150 65 NM4 101 YORK INTERNATIONAL LD02655 FIG 37C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Страница 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Страница 105: ...FORM 150 65 NM4 105 YORK INTERNATIONAL LD02657 FIG 39C GRILLE AND LOUVER INSTALLATION FRONT AND BACK...
Страница 107: ...FORM 150 65 NM4 107 YORK INTERNATIONAL FIG 40A CONDENSER COIL LOUVER INSTALLATION SIDES LD02658...
Страница 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Страница 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...