7.6 Initializing Parameter Settings (Fn005)
7-11
7
Utili
ty Fu
ncti
ons (Fn
)
7.6
Initializing Parameter Settings (Fn005)
This function is used when returning to the factory settings after changing parameter settings.
Note: Any value adjusted with Fn009, Fn00A, Fn00B, Fn00C, Fn00D, Fn00E, and Fn00F cannot be initialized by Fn005.
(1) Preparation
The following conditions must be met to initialize the parameter values.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The servo ON signal (/S-ON) must be OFF.
(2) Operating Procedure
Use the following procedure.
• Be sure to initialize the parameter settings while the servo ON (/S-ON) signal is OFF
.
• After initialization, turn OFF the power supply and then turn ON again to validate the
settings.
Step
Display after Opera-
tion
Keys
Operation
1
Press the MODE/SET Key to select the utility function.
2
Press the UP or DOWN Key to select Fn005.
3
Press the DATA/SHIFT Key for approximately one second.
The display shown on the left appears.
4
Press the MODE/SET Key. Then, the parameters will be
initialized.
When the initialization has been completed, "donE" flashes
on the display and returns to the screen as shown on the left.
5
To enable the change in the setting, turn the power OFF and ON again.
MODE/SET
DATA/
MODE/SET
DATA/
MODE/SET
DATA/
MODE/SET
DATA/
Содержание SGDV SERVOPACK
Страница 23: ...www dadehpardazan ir 88594014 15 xxii ...
Страница 53: ...www dadehpardazan ir 88594014 15 2 Panel Operator 2 10 ...
Страница 103: ...www dadehpardazan ir 88594014 15 3 Wiring and Connection 3 7 3 Connecting a Reactor for Harmonic Suppression 3 50 ...
Страница 117: ...www dadehpardazan ir 88594014 15 4 Trial Operation 4 5 4 Operator Displays during Testing without Motor 4 14 ...
Страница 203: ...www dadehpardazan ir 88594014 15 5 Operation 5 11 5 Precautions for Safety Functions 5 86 ...
Страница 275: ...www dadehpardazan ir 88594014 15 6 Adjustments 6 9 7 Position Integral 6 72 ...