6 Adjustments
6.2.2 Tuning-less Levels Setting (Fn200) Procedure
6-14
6.2.2
Tuning-less Levels Setting (Fn200) Procedure
The procedure to use the tuning-less function is given below.
Operate the tuning-less function from the panel operator, digital operator (option), or S.
For the basic operation of the digital operator, refer to
-V Series User’s Manual, Operation of Digital Opera-
tor
(No.: SIEP S800000 55).
(1) Preparation
Check the following settings before performing the tuning-less function. If the settings are not correct, "NO-
OP" will be displayed during the tuning-less function.
• The tuning-less function must be enabled (Pn170.0 = 1).
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The test without a motor function must be disabled. (Pn00C.0 = 0).
(2) Operating Procedure with Digital Operator
CAUTION
• To ensure safety, perform the tuning-less function in a state where the SERVOPACK can come to an
emergency stop at any time.
Step
Display after Operation
Keys
Operation
1
Press the
Key to view the main menu for the
utility function.
Use the
or
Key to move through the list,
select Fn200.
2
Press the
Key to display the load level of the
tuning-less mode setting screen.
Notes:
• If the response waveform causes overshooting or if
the mass of the load is 30 times greater or more
than that of the servomotor in the mass ratio (i.e.,
outside the scope of product guarantee), press the
Key and change the mode setting to 2.
• If a high-frequency noise is heard, press the
Key and change the mode setting to 0.
3
Press the
Key to display the rigidity level of the
tuning-less mode setting screen.
4
Press the
Key or the
Key to select the rigid-
ity level.
Select the rigidity level from 0 to 4. The larger the
value, the higher the gain is and the better response
performance will be. (The factory setting is 4.)
Notes:
• Vibration may occur if the rigidity level is too high.
Lower the rigidity level if vibration occurs.
• If a high-frequency noise is heard, press the
Key to automatically set a notch filter to the vibra-
tion frequency.
5
Press the
Key. “DONE” will flash for approxi-
mately two seconds and then “RUN” will be dis-
played. The settings are saved in the SERVOPACK.
㧾㨁㧺 ̆㧲㨁㧺㧯㨀㧵㧻㧺̆
㧲㨚㧜㧤㧜㧦㧼㨛㨘㨑ޓ㧰㨑㨠㨑㨏㨠
㧲㨚㧞㧜㧜㧦㨀㨡㨚㨑㧸㨢㨘ޓ㧿㨑㨠
㧲㨚㧞㧜㧝㧦㧭㧭㨀
㧲㨚㧞㧜㧞㧦㧾㨑㨒㧙㧭㧭㨀
㧾㨁㧺 ̆㨀㨡㨚㨑㧸㨢㨘㧿㨑㨠̆
ޓ㧹㨛㨐㨑㧩
㧾㨁㧺 ̆㨀㨡㨚㨑㧸㨢㨘㧿㨑㨠̆
ޓ㧸㨑㨢㨑㨘㧩㧠
㧾㨁㧺 ̆㨀㨡㨚㨑㧸㨢㨘㧿㨑㨠
̆
ޓ㧸㨑㨢㨑㨘㧩㧠
ޓޓޓޓޓ㧺㧲㧞
2nd notch filter
㧾㨁㧺 ̆㨀㨡㨚㨑㧸㨢㨘㧿㨑㨠̆
ޓ㧸㨑㨢㨑㨘㧩㧠
Содержание SGDV SERVOPACK
Страница 23: ...www dadehpardazan ir 88594014 15 xxii ...
Страница 53: ...www dadehpardazan ir 88594014 15 2 Panel Operator 2 10 ...
Страница 103: ...www dadehpardazan ir 88594014 15 3 Wiring and Connection 3 7 3 Connecting a Reactor for Harmonic Suppression 3 50 ...
Страница 117: ...www dadehpardazan ir 88594014 15 4 Trial Operation 4 5 4 Operator Displays during Testing without Motor 4 14 ...
Страница 203: ...www dadehpardazan ir 88594014 15 5 Operation 5 11 5 Precautions for Safety Functions 5 86 ...
Страница 275: ...www dadehpardazan ir 88594014 15 6 Adjustments 6 9 7 Position Integral 6 72 ...