5.4 Position Control
5-49
5
Op
er
at
io
n
5.4.8
Reference Pulse Inhibit Function
This function inhibits the SERVOPACK from counting input pulses during position control. When this func-
tion is enabled, the SERVOPACK does not accept the reference pulse input.
(1) Factory-set Input Signal Allocations (Pn50A.0 = 0)
Use Pn000.1=B and the /P-CON signal to use the reference pulse inhibit function while the input signal allo-
cations are still in the factory settings.
Note: If Pn000.1 is set to B, the /P-CON signal cannot be used for any function other than the reference pulse inhibit func-
tion.
(2) Changing Input Signal Allocations (Pn50A.0 = 1)
Allocate the /INHIBIT signal as the reference pulse inhibit signal to use the reference pulse inhibit function
while the Pn000.1 (control method) is set to 1, 5, 7, or 8.
Note: Use parameter Pn50D.1 to allocate the /INHIBIT signal for use. For details, refer to
3.3.1 Input Signal Allocations
to
Input Terminals
.
To use the reference pulse inhibit function, set Pn000.1 to 1, 5, 7 or 8.
Note: Reference pulse inhibit function is effective only with position control.
Type
Signal
Name
Connector
Pin Number
Setting
Meaning
Input
/P-CON
CN1-41
[Factory setting]
ON (closed)
Stops counting the reference pulses.
OFF (open)
Counts the reference pulses.
Parameter
Control Method
Input Signal
Used
When Enabled
Classification
Pn000
n.
B
Position Control
Position Control
with Reference Pulse Inhibit Function
/P-CON
After restart
Setup
Type
Signal
Name
Connector
Pin Number
Setting
Meaning
Input
/INHIBIT
Must be allocated.
ON (closed)
Stops counting the reference pulses.
OFF (open)
Counts the reference pulses.
Parameter
Control Method
Input Signal
Used
When Enabled
Classification
Pn000
n.
1
Position Control
/INHIBIT
After restart
Setup
n.
5
Internal Set Speed Control
Position
Control
/INHIBIT
/SPD-A
/SPD-B
/SPD-D
/C-SEL
n.
7
Position Control
Speed Control
/INHIBIT
/C-SEL
n.
8
Position Control
Force Control
/INHIBIT
/C-SEL
Содержание SGDV SERVOPACK
Страница 23: ...www dadehpardazan ir 88594014 15 xxii ...
Страница 53: ...www dadehpardazan ir 88594014 15 2 Panel Operator 2 10 ...
Страница 103: ...www dadehpardazan ir 88594014 15 3 Wiring and Connection 3 7 3 Connecting a Reactor for Harmonic Suppression 3 50 ...
Страница 117: ...www dadehpardazan ir 88594014 15 4 Trial Operation 4 5 4 Operator Displays during Testing without Motor 4 14 ...
Страница 203: ...www dadehpardazan ir 88594014 15 5 Operation 5 11 5 Precautions for Safety Functions 5 86 ...
Страница 275: ...www dadehpardazan ir 88594014 15 6 Adjustments 6 9 7 Position Integral 6 72 ...