2.4 MEMOBUS/Modbus Setup Parameters
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
265
ME
MOBUS/Mo
dbus
C
ommuni
cat
io
ns
2
Setting 0: 0.1 V Units
Setting 1: 1 V Units
■
H5-11: Communications Enter Function Selection
Selects if an Enter command is needed to change parameter values via MEMOBUS/Modbus
communications. Refer to
Setting 0: Enter Command Necessary
Parameter changes become effective after an Enter command. An Enter command must only
be sent after the last parameter change, not for each single parameter (such as in Varispeed
F7).
Setting 1: Enter Command not Necessary
Parameter value changes become effective immediately without the need to send an Enter
command (such as in Varispeed VS606-V7)
■
H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/
Modbus communications (b1-02/16 = 2).
Setting 0: FWD/Stop, REV/Stop
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive in the forward
direction. Setting bit 1 will start and stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive. Setting bit 1
changes the direction.
No.
Name
Setting Range
Default
H5-11
Communications Enter Function Selection
0 or 1
1
No.
Name
Setting Range
Default
H5-12
Run Command Method Selection
0 or 1
0
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...