2.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
283
ME
MOBUS/Mo
dbus
C
ommuni
cat
io
ns
2
00C8H
Alarm contents 2
bit 0
Undervoltage (Uv)
bit 1
Overvoltage (ov)
bit 2
Heatsink Overheat (oH)
bit 3
Drive Overheat (oH2)
bit 4
Overtorque 1 (oL3)
bit 5
Overtorque 2 (oL4)
bit 6
Run Commands Input Error (EF)
bit 7
Drive Baseblock (bb)
bit 8
External Fault 3, input terminal S3 (EF3)
bit 9
External Fault 4, input terminal S4 (EF4)
bit A
External Fault 5, input terminal S5 (EF5)
bit B
External Fault 6, input terminal S6 (EF6)
bit C
Reserved
bit D
Reserved
bit E
Cooling Fan Error (FAN)
bit F
Overspeed (oS)
00C9H
Alarm contents 3
bit 0
Excessive Speed Deviation (dEv)
bit 1
PG Disconnected (PGo)
bit 2
Digital Operator Connection Fault (oPr)
bit 3
MEMOBUS/Modbus Communication Error (CE)
bit 4
Option Communication Error (bUS)
bit 5
Serial Communication Transmission Error (CALL)
bit 6
Motor Overload (oL1)
bit 7
Drive Overload (oL2)
bit 8
Reserved
bit 9
Option Card External fault (EF0)
bit A
Motor 2 Switch command input during run (rUn)
bit B
Reserved
bit C
Serial Communication Transmission Error (CALL)
bit D
Undertorque Detection 1 (UL3)
bit E
Undertorque Detection 2 (UL4)
bit F
MEMOBUS/Modbus Test Mode Fault (SE)
Register No.
Contents
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...