1.5 E: Motor Parameters
126
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
■
E5-05: Motor Armature Resistance (PM OLV)
Set the resistance for each motor phase (not line-to-line resistance!). When measuring the
resistance manually make sure to enter the resistance of one phase into E5-05.
Note:
This parameter is not reset when the drive is initialized using A1-03.
■
E5-06: Motor d Axis Inductance (PM OLV)
Sets the d axis inductance in units of 0.01 mH.
Note:
This parameter is not reset when the drive is initialized using A1-03.
■
E5-07: Motor q Axis Inductance (PM OLV)
Sets the q axis inductance in units of 0.01 mH.
Note:
This parameter is not reset when the drive is initialized using A1-03.
■
E5-09: Motor Induction Voltage Constant 1 (PM OLV)
Set the induced phase peak voltage in units of 0.1 mV/(rad/s) [electrical angle]. Set this
parameter when using an SSR1 series IPM motor with derated torque or an SST4 series
motor with constant torque.
When E5-01 is set to “FFFF” use either E5-09 or E5-24 for setting the voltage constant.
Note:
1.
Ensure that E5-24 = 0 when setting parameter E5-09. An alarm will be triggered, however, if both E5-
09 and E5-24 are set 0, or if neither parameter is set to 0.
No.
Parameter Name
Setting Range
Default
E5-05
Motor Armature Resistance
0.000 to 65.000
Ω
Depending on
E5-01
No.
Parameter Name
Setting Range
Default
E5-06
Motor d Axis Inductance
0.00 to 300.00 mH
Depending on
E5-01
No.
Parameter Name
Setting Range
Default
E5-07
Motor q Axis Inductance
0.00 to 600.00 mH
Depending on
E5-01
No.
Parameter Name
Setting Range
Default
E5-09
Motor Induction Voltage Constant 1
0.0 to 2000.0 mV/
(rad/s)
Depending on
E5-01
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...