A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
339
Para
me
te
r Lis
t
A
Note:
Cycle power to the drive to enable MEMOBUS/Modbus settings.
◆
L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary
power loss, Stall Prevention, frequency detection, fault restarts, overtorque detection, torque
limits and other types of hardware protection.
H6-03
Pulse Train Input Gain
Sets the level of the value selected in H6-01
when a frequency with the value set in H6-02 is
input.
0.0 to
1000.0
100.0
%
A A A
42E
H6-04
Pulse Train Input Bias
Sets the level of the value selected in H6-01
when 0 Hz is input.
-100.0 to
+100.0
0.0% A A A
42F
H6-05
Pulse Train Input
Filter Time
Sets the pulse train input filter time constant.
0.00 to
2.00
0.10
s
A A A
430
H6-06
Pulse Train Monitor
Terminal MP
Selection
Select the pulse train monitor output function
(value of the -
part of U
-
).
U monitors.
Example: To select U5-01, set “501.”
When not using this parameter or when using in
the through mode, set “000”.
000,
031,
101,
102,
105,
116,
501, 502
102 A A A
431
H6-07
Pulse Train Monitor
Scaling
Sets the terminal MP output signal frequency
when the monitor value is 100%. Set H6-06 to
“2” and H6-07 to “0”, to make the pulse train
monitor output equal to the output frequency.
0 to
32000
1440
Hz
A A A
432
<22> Parameter can be changed during run.
<39> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<40> The availability of certain functions depends on the control method used.
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...