A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
307
Para
me
te
r Lis
t
A
C1-10
Accel/Decel Time
Setting Units
Sets the resolution of C1-01 to C1-09.
0: 0.01 s (0.00 to 600.00 s)
1: 0.1 s (0.0 to 6000.0 s)
0, 1
1
A A A
209
C1-11
Accel/Decel Time
Switching Frequency
Sets the frequency for automatic acceleration/
deceleration switching.
Below set frequency: Accel/Decel Time 4
Above set frequency: Accel/Decel Time 1
The multi-function input “Accel/Decel Time
1” or “Accel/Decel Time 2” take priority.
0.0 to
400.0 Hz
0.0 Hz A A A
20A
C2: S-Curve Characteristics
Use C2 parameters to configure S-curve operation.
C2-01
S-Curve Characteristic
at Accel Start
The S-curve can be controlled in the four
points shown below.
S-curve is used to further soften the starting
and stopping ramp. The longer the S-curve
time, the softer the starting and stopping
ramp.
0.00 to
10.00
0.20 s
A A A
20B
C2-02
S-Curve Characteristic
at Accel End
0.00 to
10.0
0.20 s A A A
20C
C2-03
S-Curve Characteristic
at Decel Start
0.00 to
10.0
0.20 s A A A
20D
C2-04
S-Curve Characteristic
at Decel End
0.00 to
10.0
0.00 s A A A
20E
C3: Slip Compensation
Use C3 parameters to configure the slip compensation function.
C3-01
Slip Compensation
Gain
Sets the slip compensation gain. Decides for
what amount the output frequency is boosted
in order to compensate the slip.
Note:
Adjustment is not normally required.
0.0 to 2.5
0.0
A A
−
20F
C3-02
Slip Compensation
Primary Delay Time
Adjusts the slip compensation function delay
time.
Decrease the setting when the slip
compensation response is too slow, increase it
when the speed is not stable.
Disabled when Simple V/f Control with PG
(H6-01 = 3) is used.
0 to 10000
2000
ms
A A
−
210
C3-03
Slip Compensation
Limit
Sets the slip compensation upper limit. Set as
a percentage of motor rated slip (E2-02).
Disabled when Simple V/f Control with PG
(H6-01 = 3) is used.
0 to 250 200% A A
−
211
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Run
comand
Output
frequency
Time
C2-01
C2-04
C2-02
C2-03
ON
OFF
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...