1.11 Auto-Tuning
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
247
Pa
ra
m
et
er D
et
ai
ls
1
4. Enter the motor nameplate data.
5. Start the Auto-Tuning process when prompted by the drive.
6. If Auto-Tuning was successfully performed, do a test run without the load and make any
necessary parameter adjustments.
7. If the test run was successful, do a test run with the load connected and make parameter
adjustments if necessary.
◆
Auto-Tuning Example
The following example illustrates how to perform Rotational Auto-Tuning for Open Loop
Vector Control (A1-02 = 2).
■
Set the Selected Type of Auto-Tuning
■
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note:
These instructions continue from Step 8 in “Selecting the Type of Auto-Tuning”.
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
⇒
2.
Press the
key until the Auto-Tuning display appears.
⇒
3.
Press
to begin setting parameters.
⇒
4.
Press
to display the value for T1-01.
⇒
5.
Press
to select the digit to edit.
⇒
6.
Press
and set the drive to perform Rotational Auto-Tuning
(00).
⇒
7.
Save the setting by pressing
.
⇒
8.
The display automatically returns to the display shown in Step 3.
⇒
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...