1.11 Auto-Tuning
254
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
■
T1-11: Motor Iron Loss (T1-01 = 3)
Provides iron loss information for determining the Energy Saving coefficient. If E2-10 has
been changed and the power has been cycled, the value set to E2-10 will appear as the
default in T1-11. If the value of T1-02 is not changed during Auto-Tuning data input, the
n
the drive will select a value that is typical for the motor power entered to T1-02.
No.
Name
Setting Range
Default
T1-07
Motor Base Speed
0 to 24000 r/min
1750 r/min
No.
Name
Setting Range
Default
T1-11
Motor Iron Loss
0 to 65535 W
Determined by
o2-04 and
C6-01