A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
299
Para
me
te
r Lis
t
A
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
b1-01
Frequency Reference
Selection 1
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-
17.
1: Terminals - Analog input terminal A1 or A2.
2: Memobus communications
3: Option PCB
4: Pulse Input (Terminal RP)
0 to 4
1
S S S
180
b1-02
Run Command
Selection 1
Selects the run command input source.
0: Operator - RUN and STOP keys on the
digital operator.
1: Digital input terminals
2: Memobus communications
3: Option PCB.
0 to 3
1
S S S
181
b1-03
Stopping Method
Selection
Selects the stopping method when the run
command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection Braking to Stop
3: Coast with Timer (A new run command is
ignored if received before the timer expires)
9: Simple Positioning
0 to 3, 9
0
S S S
182
DC Injection Braking at Stop
cannot be selected when using
Open Loop Vector for PM motors.
b1-04
Reverse Operation
Selection
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
0,1
0
A A A
183
b1-07
LOCAL/REMOTE
Run Selection
Determines the operation when the Run
command source is switched from LOCAL to
REMOTE or between Run source 1 and 2 while
an external Run command is active at the new
source.
0: External Run command has to be cycled at
the new source to be activated.
1: External Run command at new source is
accepted immediately.
0,1
0
A A A
186
b1-08
Run Command
Selection while in
Programming Mode
0: Run command accepted only in the operation
menu.
1: Run command accepted in all menus.
2: Prohibit entering Programming Mode during
Run
0 to 2
0
A A A
187
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...