A.2 Parameter Table
308
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
C3-04
Slip Compensation
Selection during
Regeneration
Selects slip compensation during regenerative
operation.
0: Disabled
1: Enabled
Using the Slip Compensation function during
regeneration may require a braking option to
handle momentary increasing regenerative
energy.
0,1
0
A A
−
212
C3-05
Output Voltage Limit
Operation Selection
Selects if the motor magnetic flux is reduced
during output voltage saturation.
0: Disabled
1: Enabled
0,1
0
−
A
−
213
C4: Torque Compensation
Use C4 parameters to configure Torque Compensation function.
C4-01
Torque Compensation
Gain
V/f Control: Sets the gain for the automatic
torque (voltage) boost function and helps to
produce better starting torque.
Increase this setting when using a long motor
cable or when the motor is significantly
smaller than the drive capacity.
Decrease this setting when motor oscillation
occurs. Set the value so that the current at low
speed does not exceeds the drives rated
current.
Open Loop Vector: Sets the torque
compensation function gain. Normally no
change is required.
0.00 to
2.50
1.00 A A A
215
C4-02
Torque Compensation
Primary Delay Time
Sets the torque compensation filter time.
Increase this setting when motor oscillation
occurs.
Reduce the setting if there is not enough
response from the motor.
0 to 60000
200
ms
A A A
216
C4-03
Torque Compensation
at Forward Start
Sets torque compensation at forward start as a
percentage of motor torque.
0.0 to
200.0
0.0%
−
A
−
217
C4-04
Torque Compensation
at Reverse Start
Sets torque compensation at reverse start as a
percentage of motor torque.
-200.0 to
0.0
0.0%
−
A
−
218
C4-05
Torque Compensation
Time Constant
Sets the time constant for torque
compensation at forward start and reverse
start (C4-03 and C4-04). The filter is disabled
if the time is set to 4 ms or less.
0 to
200
10 ms – A –
219
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...