2.4 MEMOBUS/Modbus Setup Parameters
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
263
ME
MOBUS/Mo
dbus
C
ommuni
cat
io
ns
2
Setting 0: No Parity
Setting 1: Even Parity
Setting 2: Odd Parity
■
H5-04: Stopping Method after Communication Error
Selects the stopping method after a communications error (CE) has occurred.
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast Stop Using C1-09
Setting 3: Alarm Only, Continue Operation
■
H5-05: Communication Fault Detection Selection
Enables or disabled the communication error (CE) detection for MEMOBUS/Modbus
communications.
Setting 0: Disabled
No error detection. The drive continues operation.
Setting 1: Enabled
If the drive does not receive data from the master for longer than the time set to H5-09, then
a CE fault will be triggered and the drive will operate as determined by parameter H5-04.
■
H5-06: Drive Transmit Wait Time
Sets the time the drive waits after receiving data from a master until responding data.
No.
Name
Setting Range
Default
H5-03
Communication Parity Selection
0 to 2
0
No.
Name
Setting Range
Default
H5-04
Stopping Method after Communication Error
0 to 3
3
No.
Name
Setting Range
Default
H5-05
Communication Fault Detection Selection
0 or 1
1
No.
Name
Setting Range
Default
H5-06
Drive Transmit Wait Time
5 to 65 ms
5 ms
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...