A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
323
Para
me
te
r Lis
t
A
◆
F: Options
F parameters are used to program the drive for PG feedback and to function with option
cards.
<38> If using a Yaskawa pico motor, the default setting is 1800 r/min.
<52> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency
Voltage 2, are set to 0.
<53> Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f
Control.
<57> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection.
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
F1: V/f Control with Simple PG Feedback - PG Setup Parameters
Use F1 parameters to set up the drive for V/f Control with Simple PG Feedback. These parameters are enabled only
when H6-01 = 03
F1-02
Operation Selection at
PG Open Circuit
(PGO)
Sets stopping method when a PG open circuit
fault (PGO) occurs. Refer to parameter F1-14.
0: Ramp to Stop - Decelerate to stop using the
active deceleration time.
1: Coast to Stop
2: Fast-stop - Decelerate to stop using the
deceleration time in C1-09.
3: Alarm only - Drive continues operation.
0 to 3
1
A
− −
381
F1-03
Operation Selection at
Overspeed (OS)
Sets the stopping method when an overspeed
(OS) fault occurs. Refer to F1-08 and F1-09.
0: Ramp to stop - Decelerate to stop using the
active deceleration time.
1: Coast to stop
2: Fast - Stop - Decelerate to stop using the
deceleration time in C1-09.
3: Alarm Only - Drive continues operation.
0 to 3
1
A
− −
382
F1-04
Operation Selection at
Deviation
Sets the stopping method when a speed
deviation (DEV) fault occurs. Refer to F1-10
and F1-11.
0: Ramp to stop - Decelerate to stop using the
active deceleration time.
1: Coast to stop
2: Fast-stop - Decelerate to stop using the
deceleration time in C1-09.
3: Alarm only - Drive continues operation.
0 to 3
3
A
− −
383
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...