1.8 L: Protection Functions
210
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
The method of incrementing the restart counter is determined by the setting of parameter L5-
05. When the counter reaches the number set in L5-01 the operation stops and the fault has
to be reset manually after correcting the cause.
The number of fault restarts is reset back to zero when:
• The drive operates normally for ten minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.
■
L5-02: Auto Restart Fault Output Operation Selection
Selects if the fault output (H2-01/02/03 = E) is set when the drive attempts to restart.
Setting 0: No Fault Output
Setting 1: Fault Output is Set
■
L5-04: Fault Reset Interval Time
Determines the amount of time to wait between attempts to restart the drive when parameter
L5-05 is set to 1.
■
L5-05: Fault Reset Operation Selection
Setting 0: Count Successful Restarts
The drive will continuously attempt to restart. If a restart trial is successful, the restart
counter is increased. This operation is repeated each time a fault occurs until the counter
reaches the value set in L5-01.
No.
Name
Setting Range
Default
L5-01
Number of Auto Restarts
0 to 10
0
No.
Name
Setting Range
Default
L5-02
Auto Restart Fault Output Operation Selection
0 or 1
0
No.
Name
Setting Range
Default
L5-04
Fault Reset Interval Time
0.5 to 600.0 s
10.0 s
No.
Name
Setting Range
Default
L5-05
Fault Reset Operation Selection
0 or 1
0
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...