A.2 Parameter Table
338
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
H5-04
Stopping Method
After Communication
Error
Selects the stopping method when a
communication time-out fault (CE) is detected.
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
0 to 3
3
A A A
428
H5-05
Communication Fault
Detection Selection
Enables or disables the communications time-
out fault (CE) detection.
0: Disabled
1: Enabled - If communication is lost for more
than two seconds, a CE fault will occur.
0,1
1
A A A
429
H5-06
Drive Transmit Wait
Time
Set the wait time between receiving and
sending data.
5 to 65 5 ms A A A
42A
H5-07
RTS Control Selection
Selects "request to send" (RTS) control:
0: Disabled - RTS is always on.
1: Enabled - RTS turns on only when sending.
0,1
1
A A A
42B
H5-09
CE Detection Time
Sets the time required to detect a
communications error. Adjustment may be
need when networking several drives.
0.0 to
10.0 s
2.0 s A A A
435
H5-10
Unit Selection for
MEMOBUS/Modbus
Register 0025H
Selects the units used for MEMOBUS/Modbus
register 0025H (Output Voltage Reference
Monitor).
0: 0.1 V units
1: 1 V units
0, 1
0
A A A
436
H5-11
Communications
ENTER Function
Selection
Select the function for the enter command that
saves parameter data to the drive.
0: Parameter changes are activated when
ENTER command is entered.
1: Parameter changes are activated immediately
without ENTER command (compatible with
Varispeed VS606-V7).
0, 1
1
A A A
43C
H5-12
Run Command
Method Selection
0: FWD/STOP, REV/STOP Method
1: RUN/STOP, FWD/REV Method
0, 1
0
A A A
43D
H6: Pulse Train Input/Output
Use H6 parameters to configure Pulse Train I/O operation.
H6-01
Pulse Train Input
Terminal RP Function
Selection
Selects pulse train input function.
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG Feedback (can
be set only when using motor 1 in V/f Control)
0 to 3
0
A A A
42C
H6-02
Pulse Train Input
Scaling
Sets the terminal RP input signal frequency that
is equal to 100% of the value selected in H6-01.
1000 to
32000
1440
Hz
A A A
42D
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...