2.4 MEMOBUS/Modbus Setup Parameters
264
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Figure 2.4
Figure 2.4 Drive Transmit Wait Time Setting
■
H5-07: RTS Control Selection
Enables or disables RTS control.
Setting 0: Disabled - RTS is Always ON
Use this setting when using RS-485 signals for communications.
Setting 1: Enabled - RTS Turns ON when Sending
Use this setting when using RS-422 signals for communications.
■
H5-09: CE Detection Time
Sets the time the communications must be lost before the drive triggers a CE fault.
■
H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H
Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.
No.
Name
Setting Range
Default
H5-07
RTS Control Selection
0 or 1
1
No.
Name
Setting Range
Default
H5-09
CE Detection Time
0.0 to 10.0 s
2.0 s
No.
Name
Setting Range
Default
H5-10
Unit Selection for MEMOBUS/Modbus Register
0025H
0 or 1
0
Command message
Response message
Command message
PLC
ψ
Drive
PLC
ψ
Drive
Drive
ψ
PLC
Time
24 bit length H5-06 setting