A.2 Parameter Table
326
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
F6-52
DeviceNet PCA
setting
I/O Polled Consuming Assembly Data Instance 0 to 255
0
A A A
3C3
F6-53
DeviceNet PPA setting I/O Polled Producing Assembly Data Instance 0 to 255
0
A A A
3C4
F6-54
DeviceNet Idle mode
fault detection
Selects if a EF0 fault is detected when no data
are received from the master.
0: Disabled
1: Enabled
0 or 1
0
A A A
3C5
F6-56
DeviceNet Speed
Scaling Factor
Sets the scaling factor for the speed monitor in
DeviceNet Class ID 2AH Object.
-15 to
15
0
A A A
3D7
F6-57
DeviceNet Current
Scaling Factor
Sets the scaling factor for the output current
monitor in DeviceNet Class ID 2AH Object.
-15 to
15
0
A A A
3D8
F6-58
DeviceNet Torque
Scaling Factor
Sets the scaling factor for the torque monitor in
DeviceNet Class ID 2AH Object.
-15 to
15
0
A A A
3D9
F6-59
DeviceNet Power
Scaling Factor
Sets the scaling factor for the power monitor in
DeviceNet Class ID 2AH Object.
-15 to
15
0
A A A 3DA
F6-60
DeviceNet Voltage
Scaling Factor
Sets the scaling factor for the voltage monitor in
DeviceNet Class ID 2AH Object.
-15 to
15
0
A A A 3DB
F6-61
DeviceNet Time
Scaling Factor
Sets the scaling factor for the time monitor in
DeviceNet Class ID 2AH Object.
-15 to
15
0
A A A 3DC
F6-62
DeviceNet Heartbeat
Interval
Sets the heartbeat interval for DeviceNet
communications.
0 to 10
0
A A A 3DD
F7-01
Ethernet IP Address 1
Combining these parameters like F7-01.F7-
02.F7-03.F7-04 sets the Ethernet IP address.
Example: (192.168.1.10).
0 to 255
192
A A A
3E5
F7-02
Ethernet IP Address 1
0 to 255
168
A A A
3E6
F7-03
Ethernet IP Address 1
0 to 255
1
A A A
3E7
F7-04
Ethernet IP Address 1
0 to 255
20
A A A
3E8
F7-05
Subnet Mask 1
Combining these parameters like F7-05.F7-
06.F7-07.F7-08 sets the Ethernet Subnet
Mask.Example: (255.255.255.0).
0 to 255
255
A A A
3E9
F7-06
Subnet Mask 2
0 to 255
255
A A A
3EA
F7-07
Subnet Mask 3
0 to 255
255
A A A
3EB
F7-08
Subnet Mask 4
0 to 255
0
A A A
3EC
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...