1.4 d: Reference Settings
102
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
When the digital operator is selected as the frequency reference source, the bias will be
added to the frequency reference that was selected 5 s after the Up/Down command has
been released, and then reset to 0 afterwards. The new frequency reference value is then
saved. When the Run command or the power supply is switched off, the drive will use the
value that was when it restarts.
Figure 1.36
Figure 1.36 Up/Down 2 Example with Reference from Digital Operator and d4-01 = 1
• Up/Down 2 with Frequency Reference Other Input Sources
When the frequency reference is set by an another source than the digital operator, the
bias value will be saved in parameter d4-06 exactly 5 s after the Up/Down 2 command has
been released. When the Run command is turned off or the power is switched off, the
drive will use the value saved in d4-06 when it restarts.
5 s
Bias
Output
frequency
Bias is added to frequency
reference and reset to 0
5 s
Up 2 command
Frequency
reference