A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
325
Para
me
te
r Lis
t
A
F6-11
CC-Link
communications speed
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
0 to 4
0
A A A
3E7
F6-14 BUS Error Auto Reset
Selects if a BUS fault can be automatically
reset.
0: Disabled
1: Enabled
0 or 1
0
A A A
3BB
F6-30 Profibus node address Sets the node address for a Profibus option.
0 to 125
0
A A A
3CB
F6-31
Profibus Clear Mode
Selection
Selects the operation when a "Clear Mode"
command is received.
0: Resets drive operation.
1: Maintains the previous operation state.
0 or 1
0
A A A
3CC
F6-32
Profibus Data Format
Selections
0: PPO Type
1: Conventional
0 or 1
0
A A A 3CD
F6-35
CANopen Node ID
selection
Sets the Node ID for a CANopen option
0 to 127 99
A A A
3D0
F6-36
CANopen
Communications
speed
0: Auto-adjust
1: 10kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
0 to 8
6
A A A
3D1
F6-40
CompoNet Node ID
Sets the Node ID for a CompoNet option.
0 to 63
0
A A A
3D5
F6-41
CompoNet Speed
0: 93.75kbit/s
1: Reserved
2: 1.5Mbit/s
3: 3Mbit/s
4: 4Mbit/s
5-255: Reserved
0 to 255
0
A A A
3D6
F6-50
DeviceNet MAC
Address
Selects the drives MAC address for DeviceNet. 0 to 63
0
A A A
3C1
F6-51
Device Net
Communications
Speed
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Adjustable from Network
4: Detect automatically
0 to 4
3
A A A
3C2
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...