2.9 MEMOBUS/Modbus Data Table
278
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
0029H
Fault Contents 2
bit 0
Reserved
bit 1
Ground Fault (GF)
bit 2
Input Phase Loss (PF)
bit 3
Output Phase Loss (LF)
bit 4
Braking Resistor Overheat (rH)
bit 5
Reserved
bit 6
Motor Overheat 2 (PTC input) (oH4)
bit 7 to bit F
Reserved
002AH
Alarm Contents1
bit 0 to bit 1
Reserved
bit 2
Run Command Input Error (EF)
bit 3
Drive Baseblock (bb)
bit 4
Overtorque Detection 1 (oL3)
bit 5
Heatsink Overheat (oH)
bit 6
Overvoltage (ov)
bit 7
Undervoltage (Uv)
bit 8
Cooling Fan Error (FAN)
bit 9
MEMOBUS/Modbus Communication Error (CE)
bit A
Option Communication Error (bUS)
bit B
Undertorque Detection 1/2 (UL3/UL4)
bit C
Motor Overheat (oH3)
bit D
PID Feedback Loss (FbL, FbH)
bit E
Serial Communication Transmission Error (CALL)
bit F
Run Command Input Error (EF)
002BH
Input Terminal Status
bit 0
Terminal S1 Closed
bit 1
Terminal S2 Closed
bit 2
Terminal S3 Closed
bit 3
Terminal S4 Closed
bit 4
Terminal S5 Closed
bit 5
Terminal S6 Closed
bit 6
Reserved
bit 7 to bit F
Reserved
Register No.
Contents
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...