1.6 F: Option Settings
130
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
◆
F6 and F7: Serial Communications Option Card Settings
These parameters are used for setting up communication option cards and communication
fault detection methods.
■
F6-01: Communications Error Option Selection
Determines the operation if a communication error occurs.
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast Stop Using C1-09
Setting 3: Alarm Only, Continue Operation
■
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option
(EF0).
Setting 0: Always Detected
Setting 1: Detection During Run Only
■
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option
(EF0).
No.
Parameter Name
Setting Range
Default
F6-01
Communications Error operation Selection
0 to 3
1
No.
Parameter Name
Setting Range
Default
F6-02
External Fault from Comm. Option Selection
0 or 1
0
No.
Parameter Name
Setting Range
Default
F6-03
External Fault from Comm. Option Operation
Selection
0 to 3
1
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...