1.11 Auto-Tuning
250
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
⇒
2.
Press the
key to select LOCAL. The LO/RE LED will
turn on.
⇒
3.
Press
to give the drive a Run command. RUN will light
and the motor will rotate at 6 Hz.
⇒
4.
Ensure the motor is rotating in the correct direction and no faults or
alarms occur.
⇒
5.
If there is no error in step 4, press
to increase the frequency
reference. Increase the frequency in 10 Hz increments verifying
smooth operation results at all speeds. For each frequency, monitor
the drive output current (U1-03) through the LED operator to
confirm the current is well below the motor rated current. Example:
6 Hz
→
50 Hz.
6.
The drive should operate normally. Press
to stop the
motor. RUN flashes until the motor comes to a complete stop.
⇒
STOP
RUN
STOP
Off
On
Motor
Forward
STOP
STOP
Flashing Off