1.7 H: Terminal Functions
180
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Figure 1.71
Figure 1.71 Analog Input Torque Limits
Setting 16: Differential PID Feedback
If an analog value is set for this function, the PID controller is set for differential feedback.
The subtraction of the PID feedback input value and the differential feedback input value
builds the feedback value that is used to calculate the PID input. Also refer to
Setting 30/31: FBD’s Analog Input 1/2
These settings are for analog output functions used by FBD’s. Normally there is no need to
change or apply these settings.
◆
H4: Multi-Function Analog Output Terminals
These parameters assign a function to analog output terminal AM for monitoring a specific
aspect of drive performance.
■
H4-01: Multi-Function Analog Terminal AM Monitor Selection
Sets the desired drive monitor parameter U -
to output as an analog value via terminal
AM. Refer to
for a list of all monitors. The “Analog Output
Level” columns indicates if a monitor can be applied for analog output or not.
Example: Enter “103” for U1-03.
positive torque reference
negative torque reference
10: Positive Torque Limit
12: Regenerative Torque Limit
15: Torque Limit
Parameter L7-04
REV motor rotation
11: Negative Torque Limit
15: Torque Limit
Parameter L7-03
10: Positive Torque Limit
15: Torque Limit
Parameter L7-01
FWD motor rotation
11: Negative Torque Limit
12: Regenerative Torque Limit
15: Torque Limit
Parameter L7-02
quadrant 2
quadrant 3
quadrant 1
quadrant 4
REV run regenerative
REV run motoring
FWD run motoring
FWD run regenerative
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...