23
S6-04
Overtorque Detection
Selection 2
(Torq Det 2 Sel)
0~6
1
0
0: No overtorque detection
1: Detection only during Speed Agree,
acceleration prohibited (continue
running). Minor error.
2: Detection while running,
acceleration prohibited (continue
running). Minor error.
3: Detection only during Speed Agree.
Interrupt output current. Serious
error.
4: Detection during run. Interrupt
output current. Serious error.
5: Detection only during Speed Agree
(continue running), but maintain
Multi-Function Digital output until
stopped. Minor error.
6: Detection druing run, but maintain
Multi-Function Digital output until
stopped. Minor error.
N
A
A
A
A
6B9H
S6-05
Overtorque Detection
Level
2
(Torq Det 2 Lvl)
0~
300
1%
150
Changed to 100% of motor rated
current in V/f Control Mode.
N
A
A
A
A
6BAH
S6-06
Overtorque Detection
Time
2
(Torq Det 2 Time)
0.0~
10.0
0.1
sec
0.1
N
A
A
A
A
6BBH
Table 4.2.2 Parameter Table (15)
Parameter Access Level
Note-2
Function
No.
Parameter Name
(Digital Operator
Display)
Setting
Range
Setting
Units
Factory
Settings
Comments
Cha
nges
on
the
Fly
V/f
V/f
w/P
G
OLV CLV
Memo
bus
Address
T 1-00
Motor 1/2
Selection
(Select Motor)
1,2
1
1
1: Motor 1 - E1 to E2
2: Motor 2 - E3 to E4
Note-2: If no motor is selected, then
this parameter will not be displayed.
N
Y
Y
Y
Y
700H
T 1-01
Autotuning Mode
Selection
(Tuning Mode Sel)
0~2
1
2
0: Rotational Auto-Tuning (A1-02 = 2
or 3)
1: Stationary Auto-Tuning (A1-02 = 2
or 3)
2: Terminal resistance only, (stationary)
N
Y
Y
Y
Y
701H
T 1-02
Motor Output
Power
(Mtr Rated Power)
0.00~
650.00
0.01
kW
0.40
*
**
*When T1-01 equals "2", then T1-02
and T1-04 are also set. T1-01 can only
be set to "2" in V/f or V/f w/PG.
**Factory/default settings will vary
based on Control Mode (refer to
attached table).
N
Y
Y
Y
Y
702H
T 1-03
Motor Rated
Voltage
(Rated Voltage)
0.0~
255.0
Note-4
0.1
VAC
200.0
Note-3
N
N
N
Y
Y
703H
T 1-04
Motor Rated
Current
(Rated Current)
0.32~
6.40
***
0.01
A
1.90
**
**Factory/default settings will vary
based on Control Mode (refer to
attached table).)
***Can be set at 10% to 200% of the
drive’s rated current.
N
Y
Y
Y
Y
704H
T 1-05
Motor Base
Frequency
(Rated Frequency)
0.0~
400.0
0.1
Hz
60.0
N
N
N
Y
Y
705H
T 1-06
Number of Motor
Poles
(Number of Poles)
2~48
2
4
N
N
N
Y
Y
706H
T 1-07
Motor Base Speed
(Rated Speed)
0~
24000
2RP
M
1750
N
N
N
Y
Y
707H
Auto
-Tuning
T 1-08
Number of PG
Pulses When
Turning
(PG Pulses/Rev)
0~
60000
1PPR
600
N
N
N
N
Y
708H
Note-3: This value is for 200V class drives. Double the value when working with 400V class drives
4.2.3 Monitor Constants Table