10
E1-03
V/f Pat tern
Selection
(V/f
Selection)
0~FF
1
F
0~E: Select from 15 preset fixed
patterns.
F : Random Pattern w/Output Voltage
Limit
FF : Random Pattern w/Output Voltage
Limit
N
Q
Q
N
N
302H
E1-04
Max Output
Frequency
(Max
Frequency)
40.0~
150.0
0.1
Hz
50.0
*
N
Q
Q
Q
Q
303H
E1-05
Max Voltage
(Max
Voltage)
0.0~
255.0
Note-3
0.1
vAC
200.0
Note-3
*
N
Q
Q
Q
Q
304H
E1-06
Base
Frequency
(Base
Frequency)
0.0~
150.0
0.1
Hz
50.0
*
N
Q
Q
Q
Q
305H
E1-07
Mid Output
Frequency
(Mid
Frequency A)
0.0~
150.0
0.1
Hz
3.0
*
N
A
A
A
A
306H
E1-08
Mid Output
Frequency
Voltage
(Mid Voltage
A)
0.0~
255.0
Note-3
0.1
vAC
12.0
Note-3
*
N
A
A
A
A
307H
E1-09
Min Output
Frequency
(Min
Frequency)
0.0~
150.0
0.1
Hz
0.5
*
N
Q
Q
Q
A
308H
E1-10
Min Output
Frequency
Voltage
(Min Voltage)
0.0~
255.0
Note-3
0.1
vAC
2.0
Note-3
*
*Factory/default settings will vary
based on Control Mode (refer to
attached table).
N
A
A
A
A
309H
E1-11
Mid Output
Frequency 2
(Mid
Frequency 2)
0.0~
150.0
0.1
Hz
0.0
**
N
A
A
A
A
30AH
E1-12
Mid Output
Frequency
Voltage 2
(Mid Voltage
2)
0.0~
255.0
Note-3
0.1
vAC
0.0
**
**Setting ignored is E1-11 and E1-12
equal zero.
N
A
A
A
A
30BH
E1-13
Base Voltage
(Base
Voltage)
0.0~
255.0
Note-3
0.1
vAC
0.0
***
***If set to 0.0, then the base voltage
will equal the maximum voltage.
N
A
A
Q
Q
30CH
E2-01
Motor Rated
Current
(Motor Rated
FLA)
***
0.1 A
(Note)
1.90
**
N
Q
Q
Q
Q
30EH
E2-02
Motor Rated
Slip
(Motor Rated
Slip)
0.00~
20.00
0.01Hz
2.90
**
N
A
A
A
A
30FH
E2-03
Motor
No-load
Current
(No-Load
Current)
0.00~
****
0.01A
1.20
**
Note: If drive capacity is 7.5kW or
less, then set in units of 0.01A.
** Factory/default settings will vary
based on Control Mode (refer to
attached table).
*** 10% to 200% of the drive’s rated
current can be set.
****The setting range for E2-03 is just
below the range for E2-01.
N
A
A
A
A
310H
E2-04
Number of
Motor Poles
(Number of
Poles)
2~48
2pole
4
N
N
Q
Q
Q
311H
Motor Parameters
E2-05
Motor
Line-to-Line
Resistance
(Term
Resistance)
0.000~
65.000
0.001O
9.842
**
**Factory/default settings will vary
based on Control Mode (refer to
attached table).
N
A
A
A
A
312H
Note-3: This value is for 200V class drives. Double the value when working with 400V class drives.
Table 4.2.2 Parameter Table (5)
Parameter Access Level
Note-2
Fu
nction
No.
Parameter Name
(Digital Operator
Display)
Setting
Range
Setting
Units
Factory
Settings
Comments
Chan
ges
on
the
Fly
V/f
V/f
w/P
G
OLV CLV
Memo
bus
Address
E2-06
Motor Leak
Inductance
(Leak Inductance)
0.0~
40.0
0.1%
18.2
**
**Factory/default settings will vary
based on Control Mode (refer to
attached table).
N
N
N
A
A
313H
Motor
Parameters
E2-07
Motor Iron-Core
Saturation
Coefficient 1
(Saturation Comp 1)
0.00~
0.50
0.01
0.50
N
N
N
A
A
314H