Table 4.2.2 Parameter Table (9)
Parameter Access Level
Note-2
Function
No.
Parameter Name
(Digital Operator
Display)
Setting
Range
Setting
Units
Factory
Settings
Comments
Cha
nges
on
the
Fly
V/f
V/f
w/P
G
OLV CLV
Memo
bus
Address
H6-01
Train Input
Function Selection
(Pulse Input Sel)
0~0
1
0
0: Frequency Reference
N
A
A
A
A
42CH
H6-02
Pulse Train Input
Scaling
(PI Scaling)
1000~
32000
1Hz
1440
Y
A
A
A
A
42DH
H6-03
Pulse Train Input
Gain
(Pulse Input Gain)
0.0~
1000.0
0.1%
100.0
Y
A
A
A
A
42EH
H6-04
Pulse Train Input
Bias
(Pulse Input Bias)
-100.0
~
100.0
0.1%
0.0
Y
A
A
A
A
42FH
H6-05
Pulse Train Input
Filter Time
(PI Filter Time)
0.00~
2.00
0.01
sec
0.10
Y
A
A
A
A
430H
H6-06
Pulse Train
Monitor Selection
(Pulse Output Sel)
*
1
2
*Outputs speed related data with the
Pulse Monitor (only U1-01, -02, -05,
-20, -31)
Y
A
A
A
A
431H
Pulse Train Input / Output
H6-07
Pulse Train
Monitor Scaling
(PO Scaling)
0~
32000
1Hz
1440
Y
A
A
A
A
432H
L1-01
Motor Protection
Selection
(MOL Fault
Select)
0~3
1
1
0: Disabled.
1: Standard Fan Cooled
2: Standard Blower Cooled
3: Vector Motor
N
Q
Q
Q
Q
480H
L1-02
Motor Protection
Time Constant
(MOL Time
Const)
0.1~
5.0
0.1
min
1.0
N
A
A
A
A
481H
L1-03
Alarm Operation
Selection During
Motor
Overheating
(MOL Thm Input)
0~3
1
3
0: Deceleration Stop
1: Coast to Stop
2: Fast Stop (Decel Time = C1-09)
3: Alarm Only (OH3 flashes on
operator)
N
A
A
A
A
482H
L1-04
Motor Overheat
Heating Operation
Selection
(MOL Filter Time)
0~2
1
1
0: Deceleration Stop
1: Coast to Stop
2: Ramp to Stop (decel time in C1-09)
N
A
A
A
A
483H
Motor Protecdtion Functions
L1-05
Motor
Temperature Input
Filter
TimeConstant
(MOL Filter Time)
0.00~
10.00
0.01
sec
0.20
N
A
A
A
A
484H
L3-01
Stall Prevention
Selection During
Accel
(StallP Accel Sel)
0~2
1
1
0: Stall Prevention Function disabled.
1: Stall Prevention Function enabled.
2: Optimum Tuning.
N
A
A
A
N
48FH
L3-02
Stall Prevention
Level During
Accel
(StallP Accel Lvl)
0~200
1%
150
N
A
A
A
N
490H
L3-03
Stall Prevention
Limit During
Accel
(StallP CHP Lvl)
0~100
1%
50
N
A
A
A
N
491H
L3-04
Stall Prevention
Selection During
Decel
(StallP Decel Sel)
0~3
Note-5
1
0
0: Stall Prevention Function disabled.
1: Stall Prevention Function enabled.
2: Optimum Tuning
3: Stall Prevention with Braking
Resistor
N
Q
Q
Q
Q
492H
L3-05
Stall Prevention
Selection During
Running
(StallP Run Sel)
0~2
1
1
0: Stall Prevention disabled.
1: Stall Prevention enabled (Decel
Time C1-02)
2: Stall Prevention enabled (Decel
Time C1-04)
N
A
A
N
N
493H
Stall Prevention
L3-06
Stall Prevention
Level During
Running
(StallP Run Level)
30~
200
1%
150
N
A
A
N
N
494H
L4-01
Speed Agreement
Detection Level
(Spd Agree Level)
0.0~
150.0
0.1
Hz
0.0
N
A
A
A
A
499H
L4-02
Speed Agreement
Detection Width
(Spd Agree Width)
0.0~
20.0
0.1
Hz
2.0
N
A
A
A
A
49AH
Frequency Detection
L4-03
Speed Agreement
Detection Level
(+/-)
(Spd Agree Lvl+-)
-150.0
~
150.0
0.1
Hz
0.0
N
A
A
A
A
49BH
Содержание CIMR-F7Z