18
o2-03
User Constant
Initial Value
(User Defaults)
0~2
1
0
0: No Change
1: Set Defaults - Saves current
parameter settings as User
Initialization..
2: Clear All - Clears the currently
saved User Initialization. A1-03
no longer allows selecting
N
A
A
A
A
507H
o2-04
kVA Selection
(Inverter Model #)
0~FF
1
0
*
*Not reset when the drive is
initialized. Factory/default settings
vary based on drive capacity.
N
A
A
A
A
508H
o2-05
Frequency
Reference Setting
Method Selection
(Operator M.O.P)
0,1
1
0
0: Disabled - Data/Enter key must be
pressed to enter a frequency
reference.
1: Enabled - Data/Enter key is not
required for the frequency
reference.
N
A
A
A
A
509H
o2-06
Operation
Selection when
Digital Operator is
Disconnected
(Oper Detection)
0,1
1
0
0: Drive will continue operatin g
even when the digital operator is
removed.
1: Removing the operator will cause
a fault.
N
A
A
A
A
50AH
o2-07
Cumulative
Operation Time
Setting
(Elapsed Time Set)
0~
65535
1H
0
N
A
A
A
A
50BH
o2-08
Cumulative
Operation Time
Selection
(Elapsed Time
Run)
0,1
1
1
0: Power-On Time - Time
accumulates when the Drive is
powered up.
1: Running Time - Time accumulates
only when the Drive is running.
N
A
A
A
A
50CH
o2-09
Initialize Mode
2
1
2
2: F7C spec
N
A
A
A
A
50DH
o2-10
Fan Operation
Time Setting
(Fan ON Time Set)
0~
65535
1H
0
N
A
A
A
A
50EH
o2-12
Fault Trace/Fault
History Clear
Functio n
(Fault Trace Init)
0,1
1
0
0: Saves the Fault Trace and Fault
History.
1: Clears both Fault Trace and Fault
History.
N
A
A
A
A
510H
o2-14
Output Power
Monitor Clear
Selection
(kWh Monitor
Ini)t
0,1
1
0
0: kWh Monitor is saved.
1: kWh Monitor reset when the drive
is initialized.
N
A
A
A
A
512H
REV-7
o3-01
Copy Function
Selection
(Copy Function
sel)
0~3
1
0
0: COPY SELECT (no function)
1: INV --> OP READ - All
parameters are copied from the
Drive to the Digital Operator.
2: OP --> INV WRITE - All
parameters are copied from the
Digital Operator to the Drive.
3: OP<-->INV VERIFY - Parameter
settings in the Drive are compared
to those in the Digital Operator.
N
A
A
A
A
515H
Copy Function
o3-02
Read Permitted
Selection
(Copy Allowable)
0,1
1
0
0: Disabled - No Digital Operator
copy functions are allowed.
1: Enabled - Copying allowed.
N
A
A
A
A
516H
Table 4.2.2 Parameter Table (12)
Parameter Access Level
Note-2
Function
No.
Parameter Name
(Digital Operator
Display)
Setting
Range
Setting
Units
Factory
Settings
Comments
Chan
ges
on
the
Fly
V/f
V/f
w/P
G
OLV CLV
Memo
bus
Address
S1-01
FWD Run Brake
Release Frequency
(Fwd Release F)
0.0~
20.0
0.1Hz
2.0
Note-6
N
A
A
A
A
680H
S1-02
REV Run Brake
Release Frequency
(Rev Release F)
0.0~
20.0
0.1Hz
2.0
Note-6
N
A
A
A
A
681H
S1-03
Brake Delay
Frequency
(Release Delay F)
0.0~
150.0
0.1Hz
3.0
*
*Factory/default settings will vary
based on Control Mode (refer to
attached table).
N
A
A
A
A
682H
S1-04
Brake Delay Time
(Release Delay T)
0.00~
10.00
0.01
sec
0.30
*
*Factory/default settings will vary
based on Control Mode (refer to
attached table).
N
A
A
A
A
683H
S1-05
FWD Run Brake
Release Current
(Fwd Release I)
0~
200
1%
50
N
A
A
A
A
684H
S1-06
REV Run Brake
Release Current
(Rev Release I)
0~
200
1%
30
N
A
A
A
A
685H
Braking Sequence
S1-07
FWD Run Brake
Release Torque
(Fwd Release T)
0~
200
1%
100
N
N
N
A
A
686H