4.1 Changes made from the standard drive:
4.1.1 Function
Differences Between the Crane Drive and F7Z Standard Drive
Added Functions
Deleted Functions
Changed Functions
Brake Sequence and Brake
Signal Observation Function
Local/Remot e Key Function
Operations changed when an external BB command is input
during run (see section 6.9).
Run Command Tuning
3-Wire Mode
Impact Stop Function
Timer Function
UV1 and UV2 detection are not executed during performing
DC Braking (during initial excitation).
Swift Lift Function
PID Control
Overload Detection Function Speed Search Function
Parameter initial values and setting range s (refer to parameter
table 4.2 for more information) are changed.
Travel Limit Function
Energy Saving Operation Function
Torque Control Mode
Name for parameter b2-04 changed to "Stop Timer" when Flux
Vector Control Mode is selected.
Momentary Power Loss
Compensation Function
Fault Restart Function
Detection Function Speed Limit
Frequency Lower Limit Function
The following setting standard for the current level has been
changed from the inverter rating to the motor rating:
? b2-02 (DC Braking Current)
? L6-02, -05 (Overtorque Detection Level 1, 2)
Magnetic Field Weakening
Motor 2 Switch Time Shortening
High Slip Braking
4.1.2 Parameter
The following parameter groups have been changed from the standard F7Z model.
Group
Standard Drive Model
Crane Drive
Changes
A1
Environment Setting
←
A1-01, -02, -03 setting range changed
b1
Operation Mode Selection
←
b1-07, -08 deleted
b2
DC Braking
←
b2-04 initial value and name changed (see p.6)
b3
Speed Search
none
Speed Search deleted
b4
Timer Function
none
Timer Function deleted
b5
PID Control
none
PID Control deleted
b6
Dwell Function
none
Dwell Function deleted
b8
Energy Saving Control
none
Energy Saving Control deleted
d5
Torque Reference
none
Torque Reference deleted
d6
Magnetic Field Weakening
none
Magnetic field control deleted
H1
Sequence Input
?
H1-03~05, change in initial value (see p.4, p.13)
H2
Sequence Output
?
H2-01, change in initial value (see p.4, p.13)
H6
Pulse Input/Output
?
H6-01 setting range change
L2
Momentary Power Loss
Compensation
none
Momentary Power Loss Compensation deleted
L3
Stall Prevention Function
?
L3-04, initial value changed (see p.15)
L5
Fault Restart
none
Fault Restart deleted
L6
Overtorque Detection
none
Overtorque detection deleted
L8
Hardware Protection
?
L8-07 initial value changed (see p.16)
n3
High Slip Braking
none
High Slip Braking deleted
o1
Display Selection
?
O1-05 deleted
o2
Operation (Key Function)
?
O1-01 deleted
S1
none
Brake Sequence
Braking sequence added
S2
none
Run Cmd Tuning Run Cmd Tuning added
S3
none
Impact Stop Function Impact Stop Function added
S4
none
Swift Lift Function Swift Lift Function added
S5
none
Overload Detection Overload Detection added
S6
none
Overtorque Detection Overtorque Detection add
U1
Monitor Contents
?
U1-24
,
U36~38 deleted, U1-48 added