8
C3-05
Output Voltage Limit
Operation Selection
(Output V Limit)
0,1
1
0
Determines if the motor magnetic
flux is automatically decreased
when output voltage saturation
occurs.
0: Disabled 1: Enabled
N
N
N
A
A
213H
C4-01
Torque
Compensation Gain
(Torq Comp Gain)
0.00~
2.50
0.01
1.00
Y
A
A
A
N
215H
Torque
Compensation
C4-02
Torque
Compensation
Primary Delay Time
Constant
(Torq Comp Time)
0~
10000
1ms
20
*
*Factory/default settings will vary
based on Control Mode (refer to
attached table).
N
A
A
A
N
216H
C5-01
ASR Proportional (P)
Gain 1
(ASR P Gain 1)
**
0.0~
300.00
0.01
20.00
*
* Factory/default settings will vary
based on Control Mode (refer to
attached table).
**If A1-02 = 03, the min setting
value is 1.00.
Y
N
A
N
A
21BH
Speed Controls
C5-02
ASR Integral (I)
Time 1
(ASR I Time 1)
0.000~
10.000
0.001
sec
0.500
*
*Factory/default settings will vary
based on Control Mode (refer to
attached table).
Y
N
A
N
A
21CH
4.2.2 Parameter Table (3)
Parameter A ccess Level
Note-2
Function
No.
Parameter Name
(Digital Operator
Display)
Setting
Range
Setting
Units
Factory
Settings
Comments
Chan
ges
on
the
Fly
V/f
V/f
w/P
G
OLV CLV
Memo
bus
Address
C5-03
ASR Proportional
(P) Gain 2
(ASR P Gain 2)
**
0.00~
300.00
0.01
20.00
*
* Factory/default settings will vary
based on Control Mode (refer to
attached table).
**If A1-02 = 03, the min setting value
is 1.00.
Y
N
A
N
A
21DH
C5-04
ASR Integral (I)
Time 2
(ASR I Time 2)
0.000
~
10.000
0.001
sec
0.500
*
*Factory/default settings will vary
based on Control Mode (refer to
attached table).
Y
N
A
N
A
21EH
C5-05
ASR Limit
(ASR Limit)
0.0~
20.0
0.1%
5.0
N
N
A
N
N
21FH
C5-06
ASR Primary
Delay Time
(ASR Delay Time)
0.000~0.
500
0.001
0.004
*Factory/default settings will vary
based on Control Mode (refer to
attached table).
N
N
N
N
A
220H
C5-07
ASR Switching
Frequency
(ASR Gain SW
Freq)
0.0~
150.0
0.1
Hz
0.0
N
N
N
N
A
221H
C5-08
ASR Integral
Limit
(ASR I Limit)
0~
400
1%
400
N
N
N
N
A
222H
C6-02
Carrier Frequency
Selection
(Carrier Freq Sel)
1~F
1
1
N
A
A
A
A
224H
C6-03
Carrier Frequency
Upper Limit
(Carrier Freq Max)
0.4~
15.0
**
***
0.1
kHz
***
N
A
A
A
A
225H
C6-04
Carrier Frequency
Lower Limit
(Carrier Freq Min)
0.4~
15.0
**
***
0.1
kHz
***
N
A
A
N
N
226H
Speed Controls
C6-05
Carrier Frequency
Proportional Gain
(Carrier Freq
Gain)
00~99
**
00
00
The Carrier Frequency is set as
follows:
1: 2.0kHz 2: 5.0kHz 3: 8.0kHz
4: 10.0kHz 5: 12.5kHz 6: 15.0kHz
F: Random
** Possible only when C6 -02 = 0F.
***Both setting range and
default/facotry settings will vary based
on drive capacity.
N
A
A
N
N
227H
d1-01
Frequency
Reference 1
(Reference 1)
0.00~
150.00
0.01
Hz
0.00
Y
Q
Q
Q
Q
280H
d1-02
Frequency
Reference 2
(Reference 2)
0.00~
150.00
0.01
Hz
0.00
Y
Q
Q
Q
Q
281H
d1-03
Frequency
Reference 3
(Reference 3)
0.00~
150.00
0.01
Hz
0.00
Y
Q
Q
Q
Q
282H
d1-04
Frequency
Reference 4
(Reference 4)
0.00~
150.00
0.01
Hz
0.00
Y
Q
Q
Q
Q
283H
d1-05
Frequency
Reference 5
(Reference 5)
0.00~
150.00
0.01
Hz
0.00
Y
A
A
A
A
284H
d1-06
Frequency
Reference 6
(Reference 6)
0.00~
150.00
0.01
Hz
0.00
Y
A
A
A
A
285H
Frequency Reference
d1-07
Frequency
Reference 7
(Reference 7)
0.00~
150.00
0.01
Hz
0.00
The setting units and setting range will
vary based on parameters E1-04 and
o1-03.
Y
A
A
A
A
286H
Содержание CIMR-F7Z
Страница 3: ......