25
U1-12
Operation
Status*
(Int Ctl Sts 1)
1: During running
1: During zero
speed
1: During reverse
1: During reset
signal input
1: During speed
agree
1: Inverter operation
ready
1: Minor fault
1: Major fault
-
A
A
A
A
4BH
U1-13
Cumulative
Operation Time
(Elapsed Time)
1H
-
A
A
A
A
4CH
U1-14
Software No.
(flash memory)*
(FLASH ID)
-
A
A
A
A
4DH
U1-15
Terminal
A1Iinput
Voltage
(Term A1 Level)
0.1%
10V:100%
A
A
A
A
4EH
Table 4.2.3 MonitorConstants Table (2)
Parameter Access Level *
3
Function
No.
Parameter Name
(Digital Operator
Display)
Setting
Range
Comments
Output Signal
Level During
Multi-Function
Analog Output
V/f
V/f
w/P
G
OLV CLV
Memo
bus
Address
U1-16
Terminal A2 Input
Voltage
(Term A2 Level)
0.1%
10V:100%
A
A
A
A
4FH
U1-18
Motor Secondary
Current (Iq)
(Mot SEC
Current)
0.1%
10V: Motor rated
secondary
current
A
A
A
A
51H
U1-19
Motor Exciting
Current (Id)
(Mot AEXC
Current)
0.1%
10V: Motor rated
secondary
current
N
N
A
A
52H
U1-20
Output Frequency
after Softstart
(SFS Output)
0.01
Hz
The unit differs depending on o1-03 setting.
10V:Max.
frequency
A
A
A
A
53H
U1-21
ASR Input
(ASR Input)
0.01%
10V:Max.
frequency
N
A
N
A
54H
U1-22
ASR Output
(ASR Output)
0.01%
Analog monitor output level becomes
10V/Max. output frequency for V/f control
mode with PG.
10V:Motor rated
secondary
current
N
A
N
A
55H
U1-25
DI-16H2 Input
Status*
(DI-16H2
Reference)
-
Displays input value according to F3 -01
setting.
For example: When lower 8 bit is ON,
Binary selection: 258, BCO selection: 99
-
A
A
A
A
58H
U1-26
Output Voltage
Reference (Vq)
(Voltage Ref(Vq))
0.1
VAC
10V:200V or
400V
N
N
A
A
59H
U1-27
Output Voltage
Reference.(Vd)
(Voltage Ref(Vd))
0.1
VAC
10V:200V or
400V
N
N
A
A
5AH
U1-28
Software No.
(CPU)
(CPU ID)
-
A
A
A
A
5BH
U1-29
Output Power
Lower 4 digits
(kWh Lower 4
dig)
kWH
-
A
A
A
A
5CH
U1-30
Output Power
Upper 5 digits
(kWh Upper 5
dig)
MWh
Monitors the Inverter ’s output power.
The display is split into upper digits and
lower digits in the following way.
□□□□□
□□□□□
kWH
U1-30 U1-29
Example:If the output power is
12345678.9 kWh, the display
will
be
as
follows:
U1-29:
678.9
kWH
U1-30: 12345 MWH
Analog monitor: (No output)
A
A
A
A
5DH
U1-32
ACR Output of q
axis
(ACR (q) Output)
0.1%
-
N
N
A
A
5FH
Status Monitor Constants
U1-33
ACR Output of d
axis
(ACR (d) Output)
0.1%
-
N
N
A
A
60H
0 0 0 0 0 0 0 0