30
Note-1: Shows the capacity when working with 1.5kW and under.
Note-2: Upper name is used in Vector Mode without PG, and the lower name is used when operating in Flux Vector Control Mode.
Note-3: Factory/default settings for E3-02, -03, -04, -05, -06, -07, and -08 will change based on the Control Mode Selection for Motor 2.
4.2.5 (1) Parameters that change based on drive capacity (o2-04):
(200V Class)
No.
Name
Units
Factory Settings
--
Inverter Capacity
E2-11
Motor rated Output
E4-07
Motor 2 Rated Output
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
o2-04
Drive/kVA Selection
1
0
1
2
3
4
5
6
7
8
9
A
C6-02
Carrier Frequency Selection
--
1
*1
1
*1
1
*1
1
*1
1
*1
1
*1
1
*1
1
*1
1
*1
1
*1
1
*1
--
Upper Limit of Carrier
Frequency
--
6
6
6
6
6
6
6
6
6
6
6
E2-01
(E4-01)
Motor Rated Current
A
1.90
3.30
6.20
8.50
14.00
19.60
26.60
39.7
53.0
65.8
77.2
E2-02
(E4-02)
Motor Rated Slip
Hz
2.90
2.50
2.60
2.90
2.73
1.50
1.30
1.70
1.60
1.67
1.70
E2-03
(E4-03)
Motor No-Load Current
A
1.20
1.80
2.80
3.00
4.50
5.10
8.00
11.2
15.2
15.7
18.5
E2-05
(E4-05)
Number of Motor Poles
?
9.842
5.156
1.997
1.601
0.771
0.399
0.288
0.230
0.138
0.101
0.079
E2-06
(E4-06)
Motor Line-to-Line
Resistance
%
18.2
13.8
18.5
18.4
19.6
18.2
15.5
19.5
17.2
20.1
19.5
E2-10
Motor Iron Loss for Torque
Compensation
W
14
26
53
77
112
172
262
245
272
505
538
L8-02
Overheat Alarm Level
ºC
95
95
100
95
95
95
95
90
100
90
90
E1-11
Motor Output Power
kW
0.40
0.75
1.50
2.20
3.70
5.50
7.50
11.00
15.00
18.50
22.00
*1 Displays 0: Low Noise PWM, 1: 2kHz, 2: 5.0kHz, 3: 8.0kHz, 4: 10kHz, 5: 12.5kHz, 6: 15kHz
(200V Class)
No.
Name
Unit
s
Factory Settings
--
Inverter Capacity
E2-11
Motor rated Output
E4-07
Motor 2 Rated Output
kW
30
37
45
55
75
90
110
o2-04
Drive/kVA Selection
kHz
B
C
D
E
F
10
11
C6-02
Carrier Frequency Selection
--
1
*1
1
*1
1
*1
1
*1
1
*1
1
*1
1
*1
--
Upper Limit of Carrier Frequency
--
4
4
4
4
4
1
1
E2-01
(E4-01)
Motor Rated Current
A
105.0
131.0
160.0
190.0
260.0
260.0
260.0
E2-02
(E4-02)
Motor Rated Slip
Hz
1.80
1.33
1.60
1.43
1.39
1.39
1.39
E2-03
(E4-03)
Motor No-Load Current
A
21.9
38.2
44.0
45.6
72.0
72.0
72.0
E2-05
(E4-05)
Number of Motor Poles
?
0.064
0.039
0.030
0.022
0.023
0.023
0.023
E2-06
(E4-06)
Motor Line-to-Line Resistance
%
20.8
18.8
20.2
20.5
20.0
20.0
20.0
E2-10
Motor Iron Loss for Torque
Compensation
699
823
852
960
1200
1200
1200
L8-02
Overheat Alarm Level
ºC
95
100
100
110
100
95
TBA
E1-11
Motor Output Power
kW
30.00
37.00 45.00
55.00
75.00
90.00
110.00
*1 Displays 0: Low Noise PWM, 1: 2kHz, 2: 5.0kHz, 3: 8.0kHz, 4: 10kHz, 5: 12.5kHz, 6: 15kHz