5.12.7 I/O signal distribution
Input signal distribution
Parameter
Parameter Meaning
Set value
Meaning
P5-20~P5-36
n. 0
Distribute input
terminal no.
0: NO signal
1: NC signal
No meaning
Basic filter time
n.0000
Not distribute to terminal input
n.000x
Input always open signal from SIx
n.0010
Set the signal to be always valid
n.001x
Input always close signal from SIx
Note: The basic filtering time refers to chapter 5.12.8.
Default setting of input terminal
Input terminal
SI1
SI2
SI3
SI4
signal
/S-ON
/ALM-RST
/P-OT
/N-OT
Output signal distribution
Parameter
Parameter Meaning
Set value
Meaning
P5-37
~
P5-47
P5-51
~
P5-53
n. 0
Distribute output
terminal no.
0: NO signal
1: NC signal
No meaning
No meaning
n.0000
Not distribute to terminal input
n.000x
Output always open signal from
SOx
n.0010
Set the signal to be always valid
n.001x
output always close signal from
SOx
Default setting of output terminal
Output terminal
SO1
SO2
SO3
Signal
/COIN
/ALM
/S-RDY
5.12.8 Input SI filter time
SI input filtering time is determined by IO parameter value and P5-18. Examples are as follows:
Pulse deviation clear set to SI1 terminal, and 30ms Filtering Time
The parameters are set as follows:
P5-34=n. 0 3 0 1
P5-34.0
P5-34.2
P5-34.0=1 input terminal is SI1
P5-34.2=3 basic filtering time is 3ms
P5-18=10 filtering time multiple is 10
So the total filtering time is P5-34.2 * P5-18=3ms*10=30ms
Содержание DS5E Series
Страница 1: ...DS5E DS5L series servo drive User manual WUXI XINJE ELECTRIC CO LTD Data No SC5 04 20190108 1 1 ...
Страница 2: ......
Страница 23: ...15 DS5E 45P5 PTA DS5E 47P5 PTA Unit mm 135 0 251 0 239 5 123 5 4 φ6 0 ...
Страница 105: ...97 2 select jog setting or manual setting to configure the inertia estimation trip 3 Set the auto tuning interface ...
Страница 117: ...109 4 Click ok to start the inertia identification 5 Configure the auto tuning parameters ...
Страница 173: ...165 ...