6.8.2 Vibration
The following causes cause machine vibration:
(1) Vibration due to inappropriate servo gain
Countermeasure: Reduce gain
(2) Mechanical resonance point
Countermeasure: Setting notch parameters manually or through mechanical characteristic analysis
6.8.3 Noise
In adaptive mode:
(1) Inappropriate servo gain
Countermeasure: Reduce the adaptive control bandwidth (P2-19).
In auto-tuning mode:
(1) Inappropriate servo gain
Countermeasure: Under the mode of rapid adjustment, reduce the rigidity level.
Automatic Adjustment Mode: Reducing Model Loop Gain P2-49
(1) Noise due to mechanical resonance
Countermeasure: Refer to 6.8.2 vibration.
7 Alarm
7.1 Alarm code list
Effective time: “√” means record the historical alarm, “empty” means not record,
“○” means can clear the alarm, “empty” means power-off clear the alarm.
Alarm
code
Code
Description
Property
Servo
status
when
alarming
type
Historical
records
Can be
cleared
EEE
E
1
EEEE1
Communication error between
panel and CPU
2
EEEE2
3
EEEE3
4
EEEE4
01
0
E-010
Firmware version mismatch
2
E-012
System Loading Error
3
E-013
FPGA Loading Error
4
E-014
FPGA Access error
5
E-015
Program running error
6
E-016
Processor Running Error
7
E-017
Processor Running Timeout
8
E-018
FPGA running timeout
9
E-019
System password error
Содержание DS5E Series
Страница 1: ...DS5E DS5L series servo drive User manual WUXI XINJE ELECTRIC CO LTD Data No SC5 04 20190108 1 1 ...
Страница 2: ......
Страница 23: ...15 DS5E 45P5 PTA DS5E 47P5 PTA Unit mm 135 0 251 0 239 5 123 5 4 φ6 0 ...
Страница 105: ...97 2 select jog setting or manual setting to configure the inertia estimation trip 3 Set the auto tuning interface ...
Страница 117: ...109 4 Click ok to start the inertia identification 5 Configure the auto tuning parameters ...
Страница 173: ...165 ...