67
Parameter
Signal
name
Default
setting
Meaning
Range
Modify Effective
P5-25
/P-CL
n.0000
The necessary
condition to use
forward
external torque
limit
Range 0000-0014, can be
distributed to other input
terminals through P5-25.
Anytime At once
P5-26
/N-CL
n.0000
The necessary
condition to use
reverse external
torque limit
Range 0000-0014, can be
distributed to other input
terminals through P5-26.
Anytime At once
3.
Relationship
The following are the relationship of internal torque limit, external torque limit, P-CL, /N-CL.
P-CL/N-CL
Final forward torque
Final reverse torque
0
Decided by P3-28
Decided by P3-29
1
The smaller one of internal forward
torque limit and external forward torque
limit
The smaller one of internal reverse
torque limit and external reverse
torque limit
4.
Output torque up to limit value signal
Parame
ter
Signal
name
Default
setting
Suitable
mode
Meaning
Modify
Effective
P5-42
Torque
limit
/CLT
n.0000
All
Output signal when
motor output torque up
to P3-28, P3-29.
Anytime
At once
No terminals are assigned by default. The parameter range is 0000-0014, which is assigned to the
output interface through parameter P5-42. When set to 0002, the signal is output from the SO2
terminal.
5.6.8 Same speed detection
(
/V-CMP
)
Parameter
Signal
Default
setting
Suitable
mode
Meaning
Modify
Effective
P5-39
/V-CMP
n.0000
3, 4, 7
Same speed
detection
Anytime
At once
Defaulted is not distribute to the terminals. Range: 0000-0014. Distribute to output terminal through
P5-39. When it set to 0002, it means output from SO2.
Parameter
Meaning
Default
setting
Unit
Range
Modify
Effective
P5-04
Same speed
detection signal
width
50
rpm
0
~
10000
Anytime
At once
There is default 10rpm hysteresis loop, please refer to chapter 5-12-3 for hysteresis loop.
5.6.9 Speed reach signal
(
/V-RDY
)
Parameter Signal
Default
setting
Suitable
mode
Meaning
Modify
Effective
P5-51
/V-RDY
n.0000
3, 4, 7
Speed reach signal
Anytime
At once
Содержание DS5E Series
Страница 1: ...DS5E DS5L series servo drive User manual WUXI XINJE ELECTRIC CO LTD Data No SC5 04 20190108 1 1 ...
Страница 2: ......
Страница 23: ...15 DS5E 45P5 PTA DS5E 47P5 PTA Unit mm 135 0 251 0 239 5 123 5 4 φ6 0 ...
Страница 105: ...97 2 select jog setting or manual setting to configure the inertia estimation trip 3 Set the auto tuning interface ...
Страница 117: ...109 4 Click ok to start the inertia identification 5 Configure the auto tuning parameters ...
Страница 173: ...165 ...