Error Flag
Description
Possible Source
Possible Action
Position Error
If the difference between
the demanded position
and the actual position
are outside the
configured limits.
Incorrect inertia or friction settings.
Binding or excessive friction in the
actuator linkage, or stops are set
inside the desired range of travel.
Check position dynamics using
the Service Tool. Click on Tools,
then click on Position
Calibration, and perform either
the manual or automatic position
calibration.
Check all mechanical linkages
and stops. Verify valve / ITB
moves freely and is not blocked
or binding.
CAN
Communications
Fault
This error is set if a CAN
Bus Off or Address Claim
error is detected.
Incorrect or intermittent wiring
problem.
Bus Off: Different device data rates.
Bus Off: Incorrect or missing
termination resistors.
Address Claim: unable to claim or
lost contention
Wrong source address.
Electrical problems within the
actuator or unit.
Check wiring for broken or loose
connection.
Verify configured data rate.
Verify proper termination resistors
at the ends of the CAN network.
Verify selected harness code.
Confirm CAN unit number on
Service Tool. Confirm no other
devices on the bus have the
same source address.
Verify configuration of CAN ID
Low and High inputs. Confirm
CAN unit number on Service
Tool. Confirm correct source
address is configured as well as
the legacy mode selection.
Possible problem with the
actuator, although additional
testing recommended before
returning to Woodward.
CAN Stop
(Run/Stop)
Shutdown
A STOP command was
received over CAN.
CAN data incorrect, CAN PGN
incorrect.
Verify PGN configuration
settings.
Verify device sending J1939
messages. A specific bit pattern
is required within the specified
PGN to trigger this STOP
command.
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...