Manual 26659
ProAct P-Series FL Position Controller
Woodward
51
Diagnostic Max Duty Cycle
Specifies the duty cycle above which a PWM input failed diagnostic is set.
Allowed values: 50-100 %. Default: 97 %
Duty Cycle Offset
Sets the PWM duty cycle offset. This setting is provided to compensate for duty
cycle variations in PWM input frequencies, voltages, and types.
Allowed values: –20 to +20 %. Default: 0 %
Analog In Tab
The analog input range is selected by the position of jumpers 3 and 5 determined
on power-up. The Analog In tab provides the analog input configuration settings
for all three input ranges.
Figure 5-4. Configuration Editor—Analog In Tab
4..20 mA Input Section
This section provides the analog input scaling and diagnostic settings, used
when the 4-20 mA range is selected.
Current Minimum
The value of the input at the output minimum setting. Setting the minimum higher
than the maximum is allowed to provide for a reverse acting signal as needed.
Allowed values: 0-25 mA. Default: 4 mA
Current Maximum
The value of the input at the output maximum setting, used for the analog input
current to position command scaling.
Allowed values: 0-25 mA. Default: 20 mA
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...