ProAct P-Series FL Position Controller
Manual 26659
80
Woodward
The ProAct P-Series FL wiring must be in accordance with North
American Class I, Division 2 or Zone 2 wiring methods as applicable,
and in accordance with the authority having jurisdiction.
The ProAct P-Series FL is used on prime movers that typically have a
high noise level. Always use appropriate hearing protection while
working around the ProAct P-Series FL.
There are two parts to the troubleshooting section:
Troubleshooting the ProAct P-Series FL
Troubleshooting Diagnostic Flags
The first section is used for situations where the system is not acting correctly,
but the ProAct P-Series FL is not giving any diagnostic flags. The second section
is used if the ProAct P-Series FL has diagnostic flags active.
Troubleshooting the ProAct P-Series FL
Problem Description
Possible Source
Possible Action
The actuator is not
communicating with
the Service Tool.
There is no power supplied to the actuator.
The wiring between the actuator and the
laptop is incorrect.
The Service Tool is disconnected.
The wrong communication port has been
selected.
Old version of Service Tool or file corruption or
bad install.
Check fuse, wiring, and battery voltage.
Check wiring according to the wiring diagram.
Connect the Service Tool by using the connect
menu.
If connected, use disconnect and then re-
connect with the correct communication port.
Check that Service Tool is running. Verify the
port setting is correct.
Re-install Service Tool, get the latest version
from the Woodward web site
(
www.woodward.com/software.aspx
).
Not controlling at
desired position
setpoint
PWM input signal inaccuracy
Measure input duty cycle and convert to
percentage. Verify actuator signal using Service
Tool. If different, adjust the PWM Offset value in
the Configuration Editor.
Scaling mismatch
Verify the value of the position setpoint using
the Service Tool. Verify the configured scaling
of the demand inputs.
Running on backup demand
Verify the demand source using the Service
Tool.
Incorrect dynamics
Incorrect position calibration
Follow the procedures in Chapter 6 for verifying
both the dynamics (inertia and friction settings)
and the position calibration.
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...