Manual 26659
ProAct P-Series FL Position Controller
Woodward
71
The following information will be sent via CAN upon request:
Software
Version
Number
The ProAct P-Series FL actuator receives the following information via CAN:
Position
Demand
Stop
command*
Reset
command*
Reset Logged faults command*
DM13
* not available in Legacy mode
CAN Message Details
Command Message (Rx)
This message is received by the ProAct P-Series FL when CAN position command is
configured.
Transmission rep rate:
5 ms minimum interval
Data length:
8 bytes
Data page:
0
PDU format:
configurable PGN
PDU specific:
configurable PGN
Suggested priority:
1 (high)
PGN:
4 configurable PGNs provided, one for each unit number
Data:
Bytes 1-2: P
osition command
Data length: 2 bytes
Resolution: 0.0025 %/bit, 0 offset
Range:
(0 to 160.6375) % (0x00 to 0xFAFF)
Note: The position demand setpoint is limited internally between 0 %
and 100 %.
Byte 3: Command bits
Data length:
1 byte
Bits 0-1: Reset Active Diagnostics
00 No action
01 Reset action *
10
Reserved
11 Not supported
Bits 2-3: Reset Logged Diagnostics
00 No action
01 Reset action *
10
Reserved
11 Not supported
Bits 4-5: Operation Control (Run/Stop)
00 No action
01
Shutdown
10
Reserved
11 Not supported
Bits 6-7: RESERVED/NOT USED
* A reset action be preceded by a no action command or the ProAct P-
Series FL will not perform the requested action - the bits cannot
remain in a ‘01’ state. The reset action occurs only upon the transition
from 00 to 01.
Bytes 4-8:
RESERVED/NOT USED (Send as 0xFF in each byte)
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...