ProAct P-Series FL Position Controller
Manual 26659
76
Woodward
ProAct P-Series FL J1939 NAME Details
Component Setting
Value
Arbitrary Address Capable Field Not Supported
0
Industry Group Field
Global
0
Vehicle System Instance Field
First Instance
0
Vehicle System Field
Non-specific system
0
Function Field
Unspecified
255
Function Instance Field
First
0
ECU Instance Field
Unit 1
Unit 2
Unit 3
Unit 4
0
1
2
3
Manufacturer Code Field
Woodward, Industrial
Controls Division
153
Identity Number Field
Unique
Unique
Table 7-2. J1939 NAME
See J1939-81 Section 4.1.1 for additional details on J1939 NAME.
Cannot Claim Address
The Cannot Claim Address message will be sent out if the P-Series receives an
Address Claimed message with the same Source Address as the receiving node
and with a higher priority (lower value) NAME. The entire 8-byte value of the
NAME is used for arbitration with the Arbitrary Address Capable Field as the
Most Significant Bit. The Cannot Claim Address will also be sent out in response
to a Request for Address Claimed if the address was unsuccessfully claimed.
The Cannot Claim Address message is identical to the Address Claimed
message in all aspects except that the Source Address of the TecJet 52 is
replaced with 254. The Cannot Claim Address message will be sent out with a
(0 to 153) ms pseudo-random delay between the reception of the triggering
message and the transmission of the Cannot Claim Address message. If the
ProAct P-Series FL cannot claim an Address, the CAN Address Claim Fault
status bit will be set.
CAN Start/Stop Broadcast (DM13)
The ability to turn off CAN message broadcasts is provided in the ProAct P-
Series FL, this feature is referred to as DM13 in the J1939 specification (see
J1939-73). This feature allows a temporary (timed) stoppage of transmitted
messages to minimize network traffic.
The ProAct P-Series FL will respond to DM13 directed to either our specific node
(our source address) or globally (FF). The following is a summary of the
Start/Stop broadcast implementation. If DM13 commands a Stop, then the
ProAct P-Series FL will stop sending all broadcast messages for 6 seconds.
During this time, if a Start is received (on byte 1.7) then message transmission
will resume; if a Hold is received (on byte 4.5) then the 6 second timer is
restarted. When the timer expires or if power is cycled on the device broadcasted
messages will be restarted.
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...