ProAct P-Series FL Position Controller
Woodward
47
Failback Inhibit
- (only displayed if configured for Redundant Demand Inputs)
When the backup demand is in control, this setting determines the max
difference between the primary and the backup demands before transferring
back into primary demand control.
Allowed values: 0.0 to 100 %. Default: 5 %
Tracking Error Section
Provides settings used to monitor how tightly redundant demand shall track and
determine which to used should they differ.
Enable Demand Tracking Fault
- (only displayed if configured for Redundant Demand
Inputs)
When selected, activates the Demand Tracking Fault logic. Default:
unchecked
Tracking Error Maximum (%)—
(only displayed if Tracking Error is used
)
Maximum deviation between the primary position demand and the backup
position demand. If the Error is exceeded for longer than the Tracking Error
Delay, then the Tracking Error Fault is annunciated.
Allowed values: (0 to 100) % but must be greater than the Failback Inhibit setting.
Default: 10 %
Tracking Error Delay (seconds)—
(only displayed if Tracking Error is used)
Delay for tracking error fault.
Allowed values: (0 to 10) seconds. Default: 1 second
Switch control to Backup demand on Track Error
– (only displayed if Tracking Error is
used)
Determines which demand input to select when a tracking error is detected,
primary or backup. When checked and a tracking error is detected, selects the
backup demand input for positioning and sets the primary demand as failed.
When unchecked, selects the primary demand and sets the backup demand as
failed.
Default: unchecked
Other Input Settings Section
Run Enable Input
Select the desired discrete input for the Run Enable function. A selection of
'Always Enabled' sets the software to always run, and acts like a 'function not
used'. Additional input settings are provided on the Discrete I/O tab.
Options: Always Enabled, Input 1, Input 2, Input 3.
Default: Always Enabled
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...