ProAct P-Series FL Position Controller
Manual 26659
96
Woodward
Transfer Function
The ProAct P-Series FL transfer function is nominally four lags and a rate limiter
(see Figure B-1 below). The first lag is an input filter is set at 0.020 seconds, with
a model-dependent slew rate limit. The second lag is set at 0.0033 seconds. The
remaining two lags are scheduled with Inertia Number as shown in the following
tables.
Figure B-1. Transfer Function
Size
Rate Limiter
(deg/s)
Model II
2285
Model III
1882
Model IV
941
Table B-1 Rate Limiter Values
Tau_3
Tau_4
Model I, II
Inertia
Number
Model III
Inertia
Number
Model IV
Inertia
Number
0.0040 0.0050
>= 16
>= 17
>= 17
0.0044 0.0063
< 16
< 17
< 17
0.0053 0.0125
< 12
< 13
< 13
0.0063 0.0250
< 7
< 8
< 8
Table B-2 Transfer Function Parameters
Inertia Settings
Inertia=Base_Inertia*1.25^InertiaNumber
The actuator with no load has inertia = Base_Inertia
Size
Base_Inertia
Model II
5.5e-4 Kg-m^2 (or N-m-s^2)
Model III
6.4e-4 Kg-m^2
Model IV
8.2e-4 Kg-m^2
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...