Manual 26659
ProAct P-Series FL Position Controller
Woodward
7
General Installation, Operation Notes and
Requirements
Do not lift or handle the P-Series by any conduit. Lift or handle the
actuator only by following proper procedures.
Use an independent device for positive shutdown, such as a fuel
shut-off valve is highly recommended. Failure to comply with this
recommendation can cause personal injury and/or property damage.
Use of an external spring to return to minimum fuel is highly
recommended. Failure to comply with this recommendation can
cause personal injury and/or property damage.
Use of a predicted min fuel shutdown procedure is highly
recommended. Failure to comply with this recommendation can
cause personal injury and/or property damage.
Unpacking and Handling
Before handling the actuator, read the Electrostatic Discharge Awareness
information on page iv. Be careful when unpacking the actuator. Check the unit
for signs of damage, such as bent or dented panels, scratches, and loose or
broken parts. If any damage is found, immediately notify the shipper.
Use both hands to pick up the ProAct P-Series FL. Do NOT pick up
by the connectors or by the terminal shaft, which could damage the
actuator or allow it to fall, with the possibility of personal injury.
Mechanical Installation
Mounting Location
The ProAct P-Series FL is designed for installation on the engine. The mounting
location on the engine has to provide suitable access to the air throttle, fuel gas
control valve, or the diesel control shaft. The ProAct P-Series FL must be able to
change the throttle, valve, or shaft position to control engine speed. Secondary
mounting location considerations are temperature, heat sink capability, vibration,
and wire length.
A minimum gap of 0.5 mm must be maintained between the support
bracket and electronics enclosure (see Figure 1-1). This is necessary
because the enclosure is supported on vibration isolators to filter out
high-frequency vibrations from reaching the electronics. If the
enclosure contacts the bracket, the isolation is defeated and may
reduce the electronics operating life.
If spacers are used to achieve the necessary gap, Woodward
recommends maximizing the surface contact area of the spacers to
maximize heat transfer between the ProAct and mounting bracket.
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...