ProAct P-Series FL Position Controller
Manual 26659
62
Woodward
Chapter 6.
Setup, Calibration, and Tuning
Introduction
This chapter describes how to setup, calibrate and tune the ProAct P-Series FL.
The Service Tool is used to configure, calibrate and tune the ProAct P-Series FL.
See Chapter 4 for Service Tool installation and connection instructions. The
actuator must be configured before it can be calibrated and tuned. The
instructions in this chapter assume the actuator has already been configured and
installed on the engine. See Chapter 5 for configuration instructions.
The following setup steps are required.
Configure the ProAct P-Series FL actuator
Calibrate
the
Position.
Calibrate the Position Feedback range.
These following optional setup features are also available:
Verify Position calibration.
Tune the Position controller loop inertia setting and friction setting.
Some applications are delivered pre-configured, calibrated, and
tuned. For these applications, the configured gains rarely need to be
changed. Min Position and Fail Direction should be checked and
verified.
An unsafe condition could occur with improper use of these software
tools. Only trained personnel should have access to these tools.
Actuator Setup
Use the Service Tool to set up the direction of rotation, either clockwise or
counterclockwise (CW or CCW), the 0 % and 100 % position feedback
calibration, and the dynamics. Ensure that the actuator linkage is set up to
maximize the actuator degrees of rotation. This results in better control
resolution.
Make sure that the actuator output shaft moves freely from the 0 % to 100 %
positions and is not blocked by any linkage, mechanical stops, etc.
It is highly recommended that the minimum fuel position setting stop
the engine. This is essential for any configured shutdowns in the
ProAct P-Series FL to be directly effective. If this is not possible, the
discrete output should be configured to actuate an external
shutdown device as needed.
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...